10-11. Items to Check Before the Test Run
(1) Turn the remote power switch ON at least 12 hours in advance in order to energize the crank case heater.
(2) Fully open the closed valves on the narrow-tube and wide-tube sides.
(3) Set the slide switch inside the wireless remote controller cover to match the unit type. After changing the set-
ting, press the ACL button.
Check that sliding switch 1 is set to "S."
S: Flap type with limit switch
(4-way, ceiling-mounted, wall-mounted)
K: Swing-only type (floor-mounted) installed
N: No-flap type (built-in)
10-12. Preparation for Test Run
10-12-1. Switching the temperature sensor
G
Temperature sensors are contained in the indoor unit and wireless remote controller. One or the other of the
temperature sensors is used for operation.
G
If
(BODY SENSOR) appears on the LCD display of the wireless remote controller, then the indoor unit body
sensor is used for operation.
To switch to the remote controller sensor, open the remote controller cover and press the SENSOR button once.
The
(BODY SENSOR) display disappears and the remote control sensor is used for operation.
NOTE
G
Even if the remote controller sensor is selected, the sensor will be automatically switched to the indoor unit body
sensor if no temperature signal has been received from the remote controller for 10 minutes. Install the remote
controller in a position where the signal can be reliably received by the unit.
G
When group control is engaged, be sure to use the body sensor.
10-12-2. Using the remote controller
G
Face the remote controller toward the receiver (on the
main unit).
G
The signal can be received up to a distance of approxi-
mately 8 m. Use this distance as a guide. This distance
may vary somewhat depending on the battery capacity
and other factors.
G
Be sure that there are no objects between the remote
controller and the receiver which may block the signal.
G
The unit beeps when a signal is received correctly.
(For operation start only, the unit beeps twice.)
G
Do not drop, throw, or wash the remote controller.
G
Do not place the remote controller in locations exposed to direct sunlight or nearby a stove.
12/13/04
11:35 AM
Page 73
Set sliding switch 2 to match
the unit type.
SKN
A: Heat-pump type
(H: Heat pump with
no auto heat/cool)
C: Cool-only type
AHC
AHC
Sliding switch 1
Fig. 10-10
73
ACL (ALL CLEAR)
button
Sensor button
Sliding switch 2
<Indicators>
OPERATION TIMER STANDBY
Receiver
Fig. 10-11