3-12. Installing the Drain Hose

a) The drain hose should be slanted downward to the
outside. (Fig. 3-32)
b) Never form a trap in the course of the hose.
c) If the drain hose will run in the room, insulate* the
hose so that chilled condensation will not damage
furniture or floors.
* Foamed polyethylene or its equivalent is recom-
mended.
WARNING
12/15/04
3:04 PM
Page 27
Do not supply power to the
unit or operate it until all
tubing and wiring to the
outdoor unit are completed.
Fig. 3-30
Insulating tape
Drain hose
Fig. 3-31
Indoor unit
Fig. 3-32
27
Insulation
Refrigerant tubing
Rear panel
Inter-unit wiring
MAFP
Slant
Refrigerant
tubing