Technibel CAFP 124 R Installation Instructions Manual page 77

Package air conditioner
Hide thumbs Also See for CAFP 124 R:
Table of Contents

Advertisement

04-393 DC INV Tech p 64-110
NOTE
* If the system address is "0," automatic address setting is performed when the power is turned ON (in the case
shown in basic wiring diagram 1).
This requires approximately 4 – 5 minutes (when the outdoor / indoor unit ratio is 1:1 as shown in basic wiring
diagram 1).
During automatic address setting, LED 1 and 2 on the outdoor unit control PCB blink alternately. These LEDs
turn OFF when automatic address setting is completed.
10-16-2. Basic wiring diagram 2
Group control (when a central control device is not used)
G
A maximum of 8 indoor units can be connected to a single remote controller.
Example: In a refrigerant system where 2 or 3 indoor units are connected to 1 outdoor unit, set the new system
address (refrigerant system address) before turning ON the remote power switch. (Refer to 10-15-3.)
(Set using the system address black rotary switch on the outdoor unit control PCB.)
Leakage breaker
Leakage breaker
Wall-mounted
Indoor
Ground
1. Wall-mounted units do not include a terminal plate for connecting a remote controller.
2. For group control of wall-mounted units, connect the remote controller crossover wiring to the remote controller connector
(2P) on the main unit, as shown in the diagram.
(Wiring procedure)
(1) Set the No. 1 wall-mounted indoor unit so that it can be operated by the wireless remote controller. (This is set
at the time of shipment.)
On the indoor unit control PCBs, set the No. 2 and following wall-mounted units to the sub remote controller.
(Refer to Item 10-16-5.)
(2) Connect the crossover wiring to 1 and 2 on the remote controller wiring terminal plates of the No. 1 indoor unit
and the other indoor units (as shown in the basic wiring diagram 2 above).
12/13/04
11:35 AM
Page 77
System address rotary switch
(Change the setting to "1".)
Leakage breaker
Outdoor unit
1 2
L
N
Ground
Inter-unit control wiring
L
Indoor
L
type
N
unit
N
No. 2
1
U1
2
U2
Ground
unit
1
No. 1
2
Connection to lead wires
(Black / White)
System address rotary switch
(Change the setting to "2".)
Outdoor unit
Leakage breaker
L
N
1 2
Ground
L
Indoor
Indoor
N
unit
unit
No. 3
No. 4
U1
U2
Ground
Ground
1
2
Remote controller crossover wiring for
group control (field-supply wiring)
2
(Thickness 0.5 – 2.0 mm
,
total length 200 m or less)
Fig. 10-14
77
Indoor power crossover
wiring – up to 16 units
(no-heater units only)
L
L
Indoor
N
N
unit
No. 5
U1
U1
U2
U2
Ground
1
1
2
2
Up to 8 units can be set
for group control