Lcd Remote Controller; Installing Procedures; Connecting Procedures; Fitting The Upper Case - Mitsubishi Electric PEA-RP200 GA Installation Manual

Indoor unit
Hide thumbs Also See for PEA-RP200 GA:
Table of Contents

Advertisement

11. LCD remote controller

11.1. Installing procedures

(1) Select an installing position for the remote controller (switch box).
Be sure to observe the following precautions.
[Fig.11.1.1] (P.6)
A Remote controller profile
B Required clearances surrounding the remote controller
C Temperature sensor
1 The temperature sensors are located on both remote controller and indoor
unit. To use the temperature sensor on the remote controller, mainly use the
remote controller for temperature setting or room temperature detection. In-
stall the remote controller in such an area that can detect average room tem-
peratures, free of direct sunlight, airflow from the air conditioner, and other
such heating source.
2 In either case when the remote controller is installed in the switch box or on the
wall, provide the clearances indicated in the diagram.
Note:
Check that there is no electric wire left close to the remote controller sensor.
If any electric wire is near the sensor, the remote controller may fail to detect
a correct room temperature.
3 Procure the following parts locally:
Switch box for two pieces
Thin copper conduit tube
Lock nuts and bushings
(2) Seal the service entrance for the remote controller cord with putty to
prevent possible invasion of dew drops, water, cockroaches or worms.
<A> For installation in the switch box:
When the remote controller is installed in the switch box, seal the junction
between the switch box and the conduit tube with putty.
<B> For direct installation on the wall select one of the following:
B-1. To lead the remote controller cord from the back of the controller:
Prepare a hole through the wall to pass the remote controller cord (in order to
run the remote controller cord from the back), then seal the hole with putty.
B-2. To run the remote controller cord through the upper portion:
Run the remote controller cord through the cut-out upper case, then seal the
cut-out notch with putty similarly as above.
[Fig. 11.1.1] (P.6)
C Wall
D Conduit
F Bushing
G Switch box
H Remote controller cord
(3) Install the lower case in the switch box or on the wall.
[Fig. 11.1.1] (P.6)
<A> For installation in the switch box
C Switch box for two pieces
E Cross-recessed, pan-head screw
G Seal the remote controller cord service entrance with putty

11.4. Function selection

<Wired remote controller type>
(1) Function selection of remote controller
The setting of the following remote controller functions can be changed using the remote controller function selection mode. Change the setting when needed.
Item 1
1. Change Language
Language setting to display
("CHANGE LANGUAGE")
2. Function limit
(1) Operation function limit setting (operation lock) ("LOCKING FUNCTION")
("FUNCTION
(2) Use of automatic mode setting ("SELECT AUTO MODE")
SELECTION")
(3) Temperature range limit setting ("LIMIT TEMP FUNCTION")
*(4) Use of automatic filter elevation panel up/down operation mode
setting
*(5) Use of fixed airflow direction mode setting
3. Mode selection
(1) Remote controller main/sub setting ("CONTROLLER MAIN/SUB")
("MODE SELECTION")
(2) Use of clock setting ("CLOCK")
(3) Timer function setting ("WEEKLY TIMER")
(4) Contact number setting for error situation ("CALL.")
(1) Temperature display °C/°F setting ("TEMP MODE °C/°F")
4. Display change
("DISP MODE SETTING")
(2) Suction air temperature display setting ("ROOM TEMP DISP SELECT")
(3) Automatic cooling/heating display setting ("AUTO MODE DISP C/H")
* This model is not equipped with this function. The setting is invalid.
D Installation pitch
E Lock nut
I Seal with putty
D Remote controller cord
Item 2
<B> For direct installation on the wall
H Wood screw
Caution:
Do not over-tighten the screws to possible deformed or broken lower case.
Note:
Select a flat place for installation.
Be sure to use two or more locations for securing of the remote control-
ler in the switch box or on the wall.

11.2. Connecting procedures

The remote controller cord can be extended up to a maximum of 200 m. Use
electric wires or (two-core) cables of 0.3 mm
tion of remote controller. Do not use multi-conductor cables to prevent possi-
ble malfunction of the unit.
[Fig. 11.2.1] (P.6)
(1) Connect the remote controller cord to the terminal block at lower case.
A To TB5 on the indoor unit
B Terminal block TB6 in remote controller
No polarity
Caution:
Do not use crimp-style terminals for connection to the remote controller
terminal block to eliminate contact with the boards and resultant trouble.
Prevent remote cord chips from getting into the remote controller. Elec-
tric shock or malfunction may result.

11.3. Fitting the upper case

[Fig. 11.3.1] (P.6)
(1) To remove the upper case, put a slotted screwdriver tip in the latches as
shown in the diagram then move the screwdriver in the direction of ar-
row.
(2) To install the upper case, put the upper latches (at two locations) first,
then fit the upper case into the lower case as illustrated.
[Fig. 11.3.2] (P.6)
Note:
Wiring hole for installing directly on the wall (or open wiring)
Cut off the shaded area from the upper case using a knife, nippers, etc.
Take out the remote control cord connected to the terminal block via this
portion.
Caution:
Do not move the screwdriver while inserting the tip far into the latches to
prevent broken latches.
Be sure to put the upper case securely in the latches by pressing it until
a snap sounds. Loosely inserted, the upper case may fall down.
Note:
The operating section is covered with a protective sheet. Before using the
unit, remember to remove the protective sheet.
Item 3 (Setting content)
• Display in multiple languages is possible.
• Setting the range of operation limit (operation lock)
• Setting the use or non-use of "automatic" operation mode
• Setting the temperature adjustable range (maximum, minimum)
• Setting the use or non-use of the automatic filter elevation panel up/down op-
eration mode
• Setting the use or non-use of the fixed airflow direction mode
• Selecting main or sub remote controller
* When two remote controllers are connected to one group, one controller must be set to sub.
• Setting the use or non-use of clock function
• Setting the timer type
• Contact number display in case of error
• Setting the telephone number
• Setting the temperature unit (°C or °F) to display
• Setting the use or non-use of the display of indoor (suction) air temperature
• Setting the use or non-use of the display of "Cooling" or "Heating" display during
operation with automatic mode
2
to 1.25 mm
2
for making connec-
13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pea-rp250 gaPea-rp400 gaPea-rp500 ga

Table of Contents