Siemens 7SR45 Argus User Manual page 61

Self powered overcurrent and earth fault relay
Hide thumbs Also See for 7SR45 Argus:
Table of Contents

Advertisement

Section 1: Commissioning and Maintenance Guide
1.1
Troubleshooting
This section provides the common problems and the recommended solution to resolve the problem.
Observation
Relay does not power
up
Relay won't accept the
password
Protection Healthy
LED OFF/LCD not
displaying
Cannot communicate
with the relay
Status inputs do not
work
Low Battery Indication
Protection Healthy
LED is not glowing
If the above troubleshooting checklist does not help in correcting the problem please contact the local Siemens
office or contact customer support, Phone: +49 180/524 8437 (24hrs), Fax: +49 180/524 2471.
E-mail:
support.energy@siemens.com
© 2017 Siemens Protection Devices Limited
Action
Check the phase connections based on the terminal diagram and CT power is
applied (or)
Check the relay is connected with USB power (or)
Check the battery is healthy
The password entered is wrong. Enter the correct password.
If correct password has been forgotten, note down the numeric code displayed at
the Change Password screen.
To retrieve the password, communicate this numeric code to a Siemens Limited
Customer representative.
The relay may have insufficient current from CT.
· Check the communication cable is connected properly.
· Check that the USB driver is installed correctly.
· In Reydisp Evolution, verify that "Do NOT Check Communications
Connection" is selected in the Advanced properties.
· In Reydisp Evolution, check that the Relay Address is set as "1" in the Relay
menu.
· Check that the correct DC voltage is applied and that the polarity is correct.
· Check that the status input settings such as the pick-up and drop-off timers
and the status inversion function are correctly set.
· Check the battery is connected with the proper polarity.
· Check the battery is healthy.
The relay may not have CT current inputs.
7SR45 Commissioning and Maintenance Guide
Chapter 4 Page 3 of 3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents