gefran 1200 Instructions For Use Manual page 27

Hide thumbs Also See for 1200:
Table of Contents

Advertisement

Protection code
P R O
This menu makes it possible to enable/disenable the display and/or modification of specific parameters and to
access the Easy configuration.
(For the access to this menu please refer to the section "Navigation in the menus of the controller")
P
r
o
PV
0
SV
Hardware configuration
KRD
This menu makes it possible to configure the Controller hardware parameters. (For the access to this menu please
refer to the section "Navigation in the menus of the controller")
K
r
d
PV
---
SV
Enabling of MultiSet, led and
K
d.
1
PV
virtual instrument status
0
SV
G
t
r
Control type
PV
6
SV
81801G_MHW_1200-1300_07-2011_ENG
Display
PRO
0
SP, IN2, alarms, 0VP, INF
1
SP, IN2, alarms, 0VP, INF
2
SP, IN2, 0VP, INF
By adding the following figures to the value in the table it is
possible to enable a series of supplementary functions:
+4:
to disable INP, 0VT
+8:
to disable [FG, SER
+16: to disable SW "power-up - power down"
+32: to disable manual power latching
+64: to disable manual power modification
+128: to enable display of all the parameters
and menus.
NOTA: 0VP and INF display only in extended configuration
First menu to set up
MultiSet
KD. 1
(2SP)
0
1
2
3
4
5
6
7
[TR
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
By adding the following figures to the value in the table it is possible to select
the sample time of the derivative action:
+0:
sample 1 sec.
+16:
sample 4 sec.
+32:
sample 8 sec.
+64:
sample 240 msec.
NOTE:
LBA alarm is not enabled with ON/OFF type control
Reversed led
Virtual instrument
status
Management via Serial
X
X
X
X
X
X
X
X
Control type
P heat
P cool
P heat / cool
PI heat
PI cool
PI heat / cool
PID heat
PID cool
PID heat / cool
ON – OFF heat
ON – OFF cool
ON – OFF heat / cool
PID heat + ON – OFF cool
ON – OFF heat + PID cool
PID heat + cool with relative gain
(see "Application Notes")
Modification
SP, alarms
SP
X
X
X
X
27

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1300

Table of Contents