RN/ER/MT LED on the interface module
Table 5- 1
RN/ER/MT status and error displays
LEDs
RN
ER
(RUN)
(ERROR)
Off
Off
On
On
Flashes
Off
Not rele-
vant
On
Not rele-
vant
Flashes
Not rele-
Not rele-
vant
vant
Flashes
Flashes
* PWR LED on (on the interface module): Check the backplane bus for a short circuit.
IM 155-6 PN ST interface module (6ES7155-6AU01-0BN0)
Manual, 04/2017, A5E03576904-AE
MT
(MAINT)
Missing or insufficient supply voltage
on interface module.
Off
Test of LEDs during startup: The three
LEDs light up simultaneously for ap-
On
proximately 0.25 s.
Interface module is deactivated.
Off
Interface module is not configured.
ET 200SP starts up.
ET 200SP is configured.
ET 200SP is reset to factory settings.
Not rele-
ET 200SP is currently exchanging data
vant
with the IO controller.
Not rele-
Group errors and group error channels. Evaluate the diagnostics data and
vant
The configured structure does not cor-
respond to the actual structure of the
ET 200SP .
Invalid configuration states.
Parameter error in the I/O module.
Maintenance
On
The "Node flash test" is run (the LEDs
LK1 and LK2 of the PROFINET inter-
Flashes
face also flash).
Hardware or firmware defective (the
LEDs LK1 and LK2 of the PROFINET
interface do not flash).
Interrupts, diagnostics, error, and system messages
Meaning
5.1 Status and error displays
Remedy
Check the supply voltage or turn in on
at the interface module. *
-
Activate the interface module with the
configuration software or the user pro-
gram.
Configure the interface module with the
configuration software.
-
remedy the error.
Check the structure of the ET 200SP to
see whether a module is missing or
defective, or whether a non-configured
module is plugged.
See section Invalid configuration states
of the ET 200SP on PROFINET IO
(Page 41)
Evaluate the display of the module
status in STEP 7 and eliminate the
error in the respective I/O module.
See section Maintenance events
(Page 36)
-
Run a firmware update. If the error
persists, contact Siemens Industry
Online Support.
Replace the interface module.
29