Lennox LNINV2610 Service Manual page 56

Refrigerant r410a

Advertisement

Start
Check wiring of the
reactor (L) of the
outdoor unit and the
PFC capacitor
Whether there is any
damage or
short-circuit?
N
Remove the PFC capacitor
and measure resistance
between the two terminals.
Is the resistance around zero?
N
Disconnect the terminals for the
reactor and measure the resistance
between the two terminals of the
reactor by an ohm gauge
Whether there is any damage
or short-circuit?
N
Replace the control
panel AP1
End
Replace it as per the
wiring diagram and
Y
reconnect the wires
The capacitor is
short circuited and
Restart the unit
Y
the capacitor
should be repla-
ced
Replace the reactor
Y
Restart the unit
If the fault is eliminated?
N
If the fault is eliminated?
N
If the fault is eliminated?
N
Y
Y
Y