Functions Indoor Unit Operation ON/OFF by Remote controller Sensing the Room Temperature • Room temperature sensor. (Thermistor) Room temperature control • Maintains the room temperature in accordance with the Setting Temp. Starting Current Control • Indoor fan is delayed for 5 seconds at the starting. Time Delay Safety Control •...
Page 12
Outdoor Unit Gas side 3-way valve Liquid side 3-way valve MODEL LT-B2421CL/HL, LT-B2461CL/HL LT-B2861HL, LT-B2821HL, LTB3021HL/HW LT-B2861CL, LT-B2821CL, LT-B3021CL/CW 74.5 74.5 –9–...
5. LT-B3681CL Outdoor Unit Wiring Diagram R S T N 3Ø, 380-415V POWER SUPPLY THMO 3(N) 4(L) GN/YL OR YL BL BK OR YL BL BK NOTE BL : BLUE RD : RED BK : BLACK WH : WHITE BR : BROWN YL : YELLOW WIRING OF FIELD OR : ORANGE...
Page 19
6. LT-B3681HL Outdoor Unit Wiring Diagram C TH T/B1 R S T N 63H2 3Ø, 380-415V POWER SUPPLY 52F2 52F1 BL BK 3(N) 4(L) GN/YL THMO OR YL BL BK OR YL BL BK 20SV BK NOTE BL : BLUE RD : RED BK : BLACK WH : WHITE...
Page 20
7. LT-B3621CL/B3621CW/B3661CL Outdoor Unit Wiring Diagram GN/YL POWER SUPPLY THMO BL BK 3(N) 4(L) GN/YL OR YL BL BK OR YL BL BK NOTE BL : BLUE RD : RED BK : BLACK WH : WHITE BR : BROWN YL : YELLOW WIRING OF FIELD OR : ORANGE GN/YL : GREEN/YELLOW...
Page 21
8. LT-B3621HL/B3621HW/B3661HL Outdoor Unit Wiring Diagram C TH T/B1 GN/YL 63H2 POWER SUPPLY 52F2 52F1 BL BK 3(N) 4(L) GN/YL THMO OR YL BL BK OR YL BL BK 20SV BK NOTE BL : BLUE RD : RED BK : BLACK WH : WHITE BR : BROWN YL : YELLOW...
Operation Details (1) The function of main control 1. Time Delay Safety Control • 3min The compressor is ceased for 3minutes to balance the pressure in the refrigeration cycle. (Protection of compressor) • 5sec Vertical louvers are delayed for 5 secs to be opened to prevent the frictional sound between louver and air flow. •...
6. Heating Mode Operation The unit will operate according to the setting by the remote controller and the operation diagram is shown as follows. Intake Air temp. minimum 3min Setting temp.+3°C (Compressor OFF) Setting temp. (Compressor ON) minimum minimum minimum 1min 10sec.
Page 24
8. Defrost Control • Defrost control is available 45 minutes later since heating mode operation started, and it will not prolong over 10 minutes. • Defrost control is carried out when the outdoor pipe temp. falls below -6°C for more than 3 minutes after 45 minutes passed from starting of heating operation.
Installation of Indoor, Outdoor Unit 1. Selection of the best location 1) Indoor unit • There should not be any heat source or steam near the unit. • There should not be any obstacles to the air cir- culation. Ceiling Ceiling Board Ceiling Board •...
Page 26
3) Piping length and the elevation Indoor unit Pipe Size Elevation B(m) * Additional Length A(m) refrigerant MODEL (g/m) Max. Max. GAS LIQUID Rated Rated 24K, 28K, 30K BTU 5/8" 3/8" 36K BTU 3/4" 3/8" Outdoor unit • Rated performance for refrigerant line length of: 5m •...
2. Ceiling opening dimensions and hanging bolt location • The dimensions of the paper model for installing are 840 (Ceiling opening) the same as those of the ceiling opening dimen- sions. 624(Hanging bolt) 800 Unit size Unit:mm CAUTION • This air-conditioner uses a drain pump. •...
3. The Indoor Unit Installation Ceiling Keep the length of the bolt Hanging bolt from the bracket to 40mm (W3/8 or M10) Flat washer for M10 Air Conditioner body (W3/8 or M10) (accessory) Ceiling board Ceiling board Spring washer (M10) Flat washer for M10 (accessory) Paper model...
WIRED REMOTE CONTROL INSTALLATION DISASSEMBLING • Separate the under plate from Remote control box. Front case Lever carefully Remote control • Fix the cord clamps on the wall by the box open box body using a screw ø 3 tapping screws (accessory). driver, etc.
5. Wiring Connection • Open the control box cover and connect the Remote control cord and Indoor power wires. Remote control cord Indoor Power wires Control Control box cover box cover fitting screw (4 units) [Air inlet side view] Wire taking inlet 1 Phase Terminal Block of Indoor Unit Terminal Block of Outdoor Unit...
ELECTRICAL WIRING 1. All wiring must comply with LOCAL REGULATIONS. 2. Select a power source that is capable of supplying the current required by the air conditioner. 3. Feed the power source to the unit via a distribution switch board designed for this purpose. 4.
6. Connecting Pipes to the Indoor Unit • Preparation of Piping Copper Main cause of gas leakage is defect in flaring Slanted Uneven Rough tube 90° work. Carry out correct flaring work in the following procedure. 1) Cutting the pipes and the cable. Use the accessory piping kit or the pipes pur- chased locally.
Piping Connection Liquid side 1. Form the piping according to its routing. Avoid bending and bending back the same piping point more than three times. (This will result in hardening Indoor of pipe.) unit 2. After deforming the piping, align centers of the Outdoor union fitting of the indoor unit and the piping, and Flare connection...
7. Installation of Decorative Panel The decorative panel has its installation Before installing the decorative panel, direction. always remove the paper template. 1. Temporarily fix two decorative panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by amount 10mm in length.) The fixing screws (hexagon M5 screw) are included the decorative panel box.
CAUTION Install certainly the decorative panel. Cool air leakage causes sweating. Water drops fall. Good example Bad example Air conditioner unit Air conditioner Cool air leakage unit (no good) Ceiling Ceiling board board Decorative Decorative panel panel Fit the insulator (this part) and be careful for cool air leakage 8.
HEAT INSULATION 1. Use the heat insulation material for the refriger- ant piping which has an excellent heat-resis- Fastening band (accessory) tance (over 120°C). 2. Precautions in high humidity circumstance: This air conditioner has been tested according to the "KS Standard Conditions with Mist" and con- firmed that there is not any default.
In case of the Outdoor Unit being installed above Seal a small opening position of the Indoor Unit. around the pipings with gum type sealer. 2. Tape the Pipings and Connecting cable from bottom to top. Trap 3. Form the pipings gathered by taping along the exterior wall, and make the trap prevent water from entering into the room.
Page 38
2) Connection of power supply 1. Connect the power supply cord to the inde- pendent power supply. • Circuit breaker is required. 2. Operate the unit for fifteen minutes or more. 3) Evaluation of the performance 1. Measure the temperature of the intake and dis- charge air.
Cycle 1. Installation (Connecting the piping between indoor and outdoor unit) Liquid side Indoor unit Outdoor unit 3-Way valve Gas side 3-Way valve Gas cylinder Purge the air • Installation (1) Connect the piping between the indoor and (5) If there is no leakage, discharge N in piping outdoor unit firmly.
Page 40
2. Disconnection (on moving) Liquid side Indoor unit Closed Outdoor unit 2-Way valve Gas side Closed 3-Way valve Retrieving Tank • Disconnection (1) Attach the charging hose (manifold gage) to (6) Disconnect the piping between indoor and the service port. outdoor unit and then put on service cap to –...
3. Gas Charging (After Evacuation) Liquid side Indoor unit Open Outdoor unit 2-Way valve Gas side Open 3-Way valve Check valve Charging cylinder OPEN CLOSE • Procedure This is different from previous procedures. (1) Connect the charge hose to the charging Because you are charging with liquid refrigerant cylinder.
Cycle Troubleshooting Guide Trouble analysis 1. Check temperature difference between intake and discharge air and operating current. Temp. difference : approx. 0°C All amount of refrigerant leaked out Current : less than 80% of Check refrigeration cycle rated current Temp. Difference Refrigerant leakege Temp.
Electronic Parts Troubleshooting Guide Possible Trouble 1 : The unit does not operate. Check the FUSE Is the input voltage and the wiring diagram. AC220V? Is the output voltage Is shorted the Check the main P.C.B of transformer about AC14V? transformer output? pattern.
Page 44
Possible Trouble 2 : The indoor fan does not operate. Is it the HOT It is normal operation. START mode? Is IC01M operated Exchange IC01M. normally? Is the each Relay Exchange Relay. any problem? Check the fan motor and connector. (CN-MOTOR) –41–...
Page 45
Possible Trouble 3 : Auto Air direction louver does not operate. Is IC01M operated Exchange IC01M. normally? Is the PIN 10 of Check the main P.C.B CN-AC2 DC12V? DC12V pattern. Check the step motor and connector. (CN-AC2, AC1) : Wired remote controller does not operate. Possible Trouble 4 Check the parts of Is the LCD operated...
Page 46
Possible Trouble 5 : Ineffective Heating Adjust operation mode. Is it Heating Mode? Does the temperature Adjust set temperature. set all right? Is IC01M operated Change IC01M. normally? Is 4way-valve operated? Check RY-4Way. Check the connector. (CN-OUT, CN-AC1.2) –43–...