8.10. Field settings table

First
Second
code
code
Setting name
0
User permission level
00
User permission level
1
Weather dependent set point
00
Low ambient temperature (Lo_A)
01
High ambient temperature (Hi_A)
02
Set point at low ambient temperature (Lo_Ti)
03
Set point at high ambient temperature (Hi_Ti)
05
Weather dependent for cooling function
enable/disable
06
Low ambient temperature (Lo2_A)
07
High ambient temperature (Hi2_A)
08
Set point at low ambient temperature (Lo2_Ti)
09
Set point at high ambient temperature (Hi2_Ti)
2
Disinfection function
00
Operation interval
01
Status
02
Start time
03
Set point (only in combination with domestic hot
water tank without electrical booster heater
(EKHTS), [4-03]=5)
03
Set point (only in combination with domestic hot
water tank with built-in electrical booster heater
(EKHW*), [4-03]≠5)
04
Interval (only in combination with domestic hot
water tank without electrical booster heater
(EKHTS), [4-03]=5)
04
Interval (only in combination with domestic hot
water tank with built-in electrical booster heater
(EKHW*), [4-03]≠5)
3
Auto restart
00
Status
4
Backup/booster heater operation and space heating off temperature
00
Backup heater operation (only in combination with
domestic hot water tank without electrical booster
heater (EKHTS))
00
Backup heater operation (only in combination with
domestic hot water tank with built-in electrical
booster heater (EKHW*))
01
Backup/booster heater priority
02
Space heating off temperature
03
Booster heater operation (only in combination with
domestic hot water tank without electrical booster
heater (EKHTS))
03
Booster heater operation (only in combination with
domestic hot water tank with built-in electrical
booster heater (EKHW*))
04
Not applicable.
05
Not applicable.
06
Backup heater emergency operation
07
Backup heater second step
(1) When the unit is configured for restricted power supply condition mode,
see
"Appendix" on page
50.
Installation manual
39
(1)
Installer setting at variance with default value
Date
Value
Date
Value
Default
value
Range
Step
3
2/3
1
–10
–20~5
1
15
10~20
1
40
25~55
1
25
25~55
1
0 (OFF)
0/1
20
10~25
1
35
25~43
1
22
5~22
1
18
5~22
1
Fri
Mon~Sun, All
1 (ON)
0/1
23:00
0:00~23:00
1:00
60
fixed
5
70
55~80
5
60
40~60
5
10
5~60
5
0 (ON)
0/1
1 (ON)
0/1/2
1 (ON)
0/1
0 (OFF)
0/1/2
25
14~25
1
5
fixed
3
0/1/2/3/4
1 (enabled)
0/1
1
1 (enabled)
0/1
1
EKHBX008BB3V3S
Indoor unit for air to water heat pump system
4PW62597-1 – 10.2010
Unit
°C
°C
°C
°C
°C
°C
°C
°C
hour
°C
°C
min
min
°C