NOTE: • The sensors have arrows to indicate a direction.
• All sensors should face the same direction.
• All sensors should have the same number of wraps.
• Sensors should encircle both leg AND ground system.
3. On the Model 6474, set the INPUT selection switch accordingly. You can mea-
sure the current flowing through one GroundFlex
through several sensors (1, 2 or 1, 2, 3), or through all of the sensors (1, 2, 3,
4).
4. Select how many times the sensor is wrapped around the conductor to be
measured (from 1 to 4 turns) using the SENSOR TURNS selection switch.
NOTE: To increase measurement sensitivity, we recommend when possible,
wrapping a maximum number of turns (up to 4) around the structure.
5.
Set the SENSITIVITY switch to the desired sensitivity: x1/10, x1, or x10. The
choice of sensitivity depends on the expected current value. As a precaution,
always start with the lowest sensitivity, x1/10, and increase it as needed.