E3 error

:
# Check the evaporator fan for correct operation. If the fan motor is not operating check the CN4 &
CN25 connector plugs for correct anchoring to the indoor main PCB.

CN4 connector plug point on indoor main PCB.

CN25 connector plug point on indoor main
PCB.
If E3 fault has not cleared:
# Check for supply AC voltage between the CN1 Neutral connector point & the "centre pin" of the CN4
connector socket located on the indoor main PCB.
Note: If supply voltage is available at these two points & E3 error still exists, replace the indoor fan
motor.

CN4 connector plug socket.

CN1 Neutral connector point.
Page 32 KSSSI90