Siemens SITRANS LG270 Operating Instructions Manual page 98

Guided wave radar
Table of Contents

Advertisement

Bristol ControlWave Micro
Wiring plan
1
+8
+30 Vdc
to
3
Fig. 56: Connection of SITRANS LG270 to RTU Bristol ControlWave Micro
1
SITRANS LG270
2
RTU Bristol ControlWave Micro
3
Voltage supply
Parameter
Parameter
Baud Rate
Floating Point Format Code
RTU Data Type
Input Register Base Number
The basic number of the input registers is always added to the input register address of SITRANS
LG270.
Address 1303 must hence be entered as register address for 1302 for RTU Bristol ControlWave
Micro.
98
GND
SITRANS LG270 - Operating Instructions
RS 485 on COM1
1 +SV
2 RX-
3 TX-
4 GND
5 RXT
6 TXT
7 not used
8 not used
Value
9600
2 (FC4)
32-bit registers as 2 16-bit registers
1
2
PBD-51041066