Siemens SITRANS LG270 Operating Instructions Manual page 42

Guided wave radar
Table of Contents

Advertisement

Setup - HART variables
(1)
Setup - HART variables
(2)
Setup - False signal sup-
pression
42
Since the HART variables are very extensive, the indication was
divided into two menu items.
In the menu "HART variables 1" you can have the first HART value PV
(primary value) and the second HART value SV (secondary value) of
the sensor displayed.
The values cannot be changed in the display and adjustment module.
To change these values, you have to use the adjustment software
PACTware.
In the menu "HART variables 2" you can have the third HART value
TV (third value) and the fourth HART value QV (quarter value) of the
sensor displayed.
The values cannot be changed in the display and adjustment module.
To change these values, you have to use the adjustment software
PACTware.
The following circumstances cause interfering reflections and can
influence the measurement:
High sockets
Vessel installations such as struts
Note:
A false signal suppression detects, marks and saves these false
signals so that they are no longer taken into account for the level and
interface measurement. We generally recommend carrying out a false
signal suppression to achieve the best possible accuracy. This should
be done with the lowest possible level so that all potential interfering
reflections can be detected.
Proceed as follows:
Enter the actual distance from the sensor to the product surface.
SITRANS LG270 - Operating Instructions
PBD-51041066