Setup - Current output,
adjustment
Setup - Current output
mode
Setup - Current output
Min./Max.
Setup - Current output 2
PBD-51041066
In menu item "Current output, adjustment" you can assign a respec-
tive measured value to the current output.
In the menu item "Current output mode" you determine the output
characteristics and reaction of the current output in case of failure.
The default setting is output characteristics 4 ... 20 mA, failure mode
< 3.6 mA.
In the menu item "Current output Min./Max.", you determine the reac-
tion of the current output during operation.
The default setting is min. current 3.8 mA and max. current 20.5 mA.
If a supplementary electronics with an additional current output is
implemented in the instrument, then you can adjust the additional
current output separately.
In menu item"Current output 2" you specify which measured value
the additional current output refers to.
The procedure corresponds to the previous settings of the standard
current output. See "Setup - Current output".
SITRANS LG270 - Operating Instructions
41