Modbus Register - Siemens SITRANS LG270 Operating Instructions Manual

Guided wave radar
Table of Contents

Advertisement

General configuration of the host
The data exchange with status and variables between field device and host is carried out via
register. For this, a configuration in the host is required. Floating point numbers with short prevision
(4 bytes) according to IEEE 754 are transmitted with individually selectable order of the data bytes
(byte transmission order). This "Byte transmission order" is determined in the parameter "Format
Code". Hence the RTU knows the registers of the SITRANS LG270 which must be contacted for the
variables and status information.
Format Code
0
1
2
3

10.3 Modbus register

Holding Register
The Holding registers consist of 16 bit. They can be read and written. Before each command, the
address (1 byte), after each command, a CRC (2 byte) is sent.
Register Name
Register Num-
ber
Address
200
Baud Rate
201
Parity
202
Stopbits
203
Delay Time
206
Byte Oder (Float-
3000
ing point format)
Input register
The input registers consist of 16 bits. They can only be read out. Before each command, the ad-
dress (1 byte) is sent, after each command a CRC (2 bytes) is sent.
PV, SV, TV and QV can be adjusted via the sensor DTM.
Register Name
Register Number
Status
100
PV Unit
104
PV
106
86
Byte transmission order
ABCD
CDAB
DCBA
BADC
Type
Configurable
Values
Word
1 ... 255
Word
1200, 2400,
4800, 9600,
19200
Word
0 = None, 1 =
Odd, 2 = Even
Word
1 = None, 2 =
Two
Word
10 ... 250
Word
0, 1, 2, 3
Type
Note
DWord
Bit 0: Invalid Measurement Value PV
Bit 1: Invalid Measurement Value SV
Bit 2: Invalid Measurement Value TV
Bit 3: Invalid Measurement Value QV
DWord
Unit Code
Primary Variable in Byte Order CDAB
SITRANS LG270 - Operating Instructions
Default Value
Unit
246
-
9600
-
0
-
1
-
50
ms
0
-
PBD-51041066