Clock Functions; Control Functions - Siemens RMH760 Manual

Heating controllers
Table of Contents

Advertisement

Functions
Note
Room operating modes

Clock functions

Holiday functions
Ready configured inputs
Freely configurable in-
puts
Note
Remote operation

Control functions

Limitation functions
2/16
Siemens Building Technologies
HVAC Products
Several of the functions listed require extension modules.
Room operating modes are:
• AUTO: Automatic changeover between 3 setpoints according to the time program
• Comfort: Continuously heating to the Comfort setpoint
• Precomfort: Continuously heating to the Precomfort setpoint
• Economy: Continuously heating to the Economy setpoint
• Protective mode: Heating to the setpoint of Protective mode, if necessary
• Year clock with automatic summer-/wintertime changeover
• 7-day clocks for time program with a maximum of 6 switching points per day
• Holiday and special day program with 16 periods per year
• Selectable room operating mode for the holiday periods
• Selectable DHW operating mode for the holiday periods
• Time program for special days
2 ready configured inputs for:
• Flow temperature (averaging possible)
• Outside temperature
3 freely configurable inputs, optionally for:
• Reception of the following measuring signals:
Room temperature (averaging possible)
Return temperature
Wind speed
Intensity of solar radiation
• Connection of a remote setpoint adjuster with relative or absolute room setpoint
adjustment
• Connection of an external switch for:
Operating mode changeover
Timer function
Changeover to holiday mode
Changeover to special day
Indication of faults
If more than 3 configurable inputs are required, extension modules must be used.
Remote operation with multifunctional room unit via Konnex bus
• Heating circuit controller
Weather-compensated flow temperature control via the heating circuit mixing
valve, with adjustable setpoints of Comfort, Precomfort, Economy and Protective
mode
Adjustable influence of room temperature, solar radiation and wind
Optimized setback and heating up
Boost heating and quick setback
Automatic heating limit for demand-dependent control of the heating with adjust-
able heating limits for the Comfort and Economy modes
Automatic changeover to summer operation (heating off)
Room model for room functions without room sensor
• Primary controller
Demand-dependent precontrol via the mixing valve in the common flow, based on
the received heat demand signals
• Maximum limitation of the room temperature
• Minimum and maximum limitation of the flow temperature
• Minimum or maximum limitation of the return temperature
Data sheet RMH760
CE1N3131en
03.07.2003