Electromagnetic Compatibility Tests - ABB RET630 Product Manual

Transformer protection and control
Table of Contents

Advertisement

Transformer Protection and Control
RET630
Product version: 1.0
Table 21. Electromagnetic compatibility tests
Description
100 kHz and 1 MHz burst
disturbance test
• Common mode
• Differential mode
Electrostatic discharge test
• Contact discharge
• Air discharge
Radio frequency interference
tests
• Conducted, common mode
OK
• Radiated, pulse-modulated
• Radiated, amplitude-
modulated
Fast transient disturbance
tests
• Communication ports
• Other ports
Surge immunity test
• Binary inputs
• Communication
• Other ports
Power frequency (50 Hz)
magnetic field
20
Type test value
2.5 kV
1.0 kV
8 kV
15 kV
10 V (emf), f=150 kHz...80
MHz
10 V/m, f=900 MHz
20 V/m (rms), f=80...1000
MHz
10 V/m, f=80...2700 MHz
2 kV
4 kV
2 kV line-to-earth, 1kV line-to-
line
1 kV line-to-earth
4 kV line-to-earth, 2 kV line-
to-line
1MRS756788 A
Issued: 15.09.2009
Reference
IEC 61000-4-18
IEC 60255-22-1, level 3
IEC 61000-4-2
IEC 60255-22-2, level 4
IEEE C37.90.3
IEC 61000-4-6
IEC 60255-22-6, level 3
ENV 50204
IEC 60255-22-3
IEEE C37.90.2-2004
IEC 61000-4-3
IEC 60255-22-3
IEC 61000-4-4
IEC 60255-22-4, class A
IEC 61000-4-5
IEC 60255-22-5, level 4/3
IEC 61000-4-8, level 5
ABB