Control Functions; Operation Characteristics; Synchrocheck (Syncrsyn) - ABB RET630 Product Manual

Transformer protection and control
Table of Contents

Advertisement

Transformer Protection and Control
RET630
Product version: 1.0
Table 67. Operation characteristics
Parameter
Operating curve type
Operating curve type (voltage protection)

Control functions

Table 68. Synchrocheck (SYNCRSYN)
Characteristic
Operation accuracy
Reset time
Reset ratio
Operate time accuracy
46
Values (Range)
1=ANSI Ext. inv.
2=ANSI Very. inv.
3=ANSI Norm. inv.
4=ANSI Mod inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
5=ANSI Def. Time
15=IEC Def. Time
17=Inv. Curve A
18=Inv. Curve B
19=Inv. Curve C
20=Programmable
21=Inv. Curve A
22=Inv. Curve B
23=Programmable
Value
At the frequency f = f
n
Voltage: ±1.0% or ±0.002 x U
Frequency: ±10 mHz
Phase angle ±2°
< 50 ms
Typical 0.96
±1.0% of the set value or ±20 ms
1MRS756788 A
Issued: 15.09.2009
n
ABB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents