core balance current transformer or from
another set of phase current transformers.

15. Access control

To protect the IED from unauthorized access
and to maintain information integrity the IED
is provided with an authentication system
including user management. Using the IED
user management tool in the Protection and
Control IED Manager PCM600, an individual
password is assigned to each user by the
administrator. Further, the user name is
associated to one or more of the four
available user groups: System Operator,
Protection Engineer, Design Engineer and
User Administrator. The user group
association for each individual user enables
the use of the IED according to the profile of
the user group.

16. Inputs and outputs

Depending on the hardware configuration
selected, the IED is equipped with six phase-
current inputs (three inputs for the HV side
and three inputs for the LV side) and one or
two neutral-current inputs for earth-fault
protection.
Depending on the selected hardware
configuration the IED includes two or three
Table 3. Analog input options
Analog input
configuration
AA
AB
AC
voltage inputs. One of the voltage inputs can
be used as a residual voltage input for
directional earth-fault protection or residual
voltage protection. The voltage inputs can
also be used as phase-voltage inputs for
overvoltage, undervoltage and directional
overcurrent protection and other voltage
based protection functions.
The phase-current inputs are rated 1/5 A.
Depending on the selected hardware
configuration the IED is equipped with one
or two alternative residual-current inputs, that
is 1/5 A or 0.1/0.5 A. The 0.1/0.5 A input is
normally used in applications requiring
sensitive earth-fault protection and featuring
a core-balance current transformer.
The voltage inputs, for either phase-to-phase
voltages or phase-to-earth voltages, and the
residual-voltage input cover the rated
voltages 100 V, 110 V, 115 V and 120 V. The
rated values of the current and voltage inputs
are selected in the IED software. In addition,
the binary input thresholds are selected by
adjusting the IED's parameter settings. The
threshold voltage can be set separately for
each binary input.
All binary input and output contacts are
freely configurable using the signal matrix of
the application configuration function in
PCM600. Please refer to the Input/output
overview tables, the selection and ordering
data, and the terminal diagrams for more
detailed information about the inputs and
outputs.
CT (1/5 A)
CT sensitive
(0.1/0.5 A)
7
8
7
1MRS756788 A