Quick Setup - Allen-Bradley SMC-50 Quick Start Manual

Smart motor controller
Hide thumbs Also See for SMC-50:
Table of Contents

Advertisement

Parameter
Parameter
Description/Function
Number
Name
46
Line Voltage
Enter the system 3-phase line voltage value. A value must be entered for the voltage protection
functions to work properly.
47
Rated Torque
Use for Torque Ramp Rating Starting Mode. Enter the maximum motor rating in Newton meters. 1...1000 N•m
48
Rated Speed
Use for Torque Ramp Rating Starting Mode. Enter the rated speed of the motor.
49
Starting Mode
Enter the desired starting mode for the application.
Related Parameters for the Starting Mode:
Full Voltage: None
Current Limit: Current Limit Level, Ramp Time, Kickstart Time, Kickstart Level
Soft Start: Initial Torque, Ramp Time, Current Limit, Kickstart Time, Kickstart Level
Linear Speed: Initial Torque, Ramp Time, Current Limit
Torque Ramp: Starting Torque, Maximum Torque, Ramp Time, Current Limit, Kickstart Time,
Kickstart Level
Pump Start: Initial Torque, Ramp Time
50
Ramp Time
Enter the amount of desired time for the motor starting ramp to take.
51
Initial Torque
Motor torque level at which the start ramp begins.
52
Maximum
Use the Torque Ramp Starting mode. Enter the maximum motor torque at the end of the required
start ramp for the application.
Torque
53
Current Limit
Enter the value of the maximum current that is allowed during the ramp time.
Level
56
Input 1
Allows the selection of how input 1 (CM terminal #11) affects the function of the SMC-50
controller.
57
Input 2
Allows the selection of how input 2 (CM terminal #10) affects the function of the SMC-50
controller.
65
Stop Mode
Enter the desired stopping mode for the application.
Related Parameters to the Stopping Mode:
Coast: None Soft Stop: Stop Time Linear Speed: Stop Time, Current Limit Pump Stop: Stop Time
SMB: Braking Current Ext. Brake: Stop Time
66
Stop Time
Defines the desired time to ramp from run to stop for a specific stop mode. For Ext Brake mode,
the Stop Time = the time the Aux contact is closed to energize an external brake.
75
Overload Class
Enter the desired motor overload trip class.
77
Service Factor
Enter the Service Factor of the motor.
78
Motor FLC
Enter the motor specified Full Load Current (FLC) value. This value must be entered to and the
controller can provide proper motor current (such as overload) protection.
172
Aux1
Allows selection of the operation for Auxiliary relay output contact #1 (control module terminals
Configuration
#4 and #5).
176
Aux 2
Allows selection of the operation for Auxiliary relay output contact #1 (control module terminals
Configuration
#6 and #7).
(1) Normal = The contact is closed when the Start command is initiated and remains closed during a stop maneuver. After the stop is complete, the contact opens.

Quick Setup

Access the basic programming configuration group in the Setup category. This
group provides a limited parameter set, which allows quick startup with
minimal adjustments.
Table 12 - Quick Start Parameters
(1)
(1)
Rockwell Automation Publication 150-QS003E-EN-P - April 2017
Programming
Value(s)
Default
0...700V
480
10
750, 900, 1500, 1800,
1800
3500, 3600 RPM
Full Voltage, Current Limit, Soft Start,
Soft Start
Linear Speed, Torque Ramp,
Pump Start
0.0...1000 seconds
10
0...90%LRT
70
0...300%
250
50...600% FLC
350
Disable, Start, Coast,
Start/Coast
Stop Option, Start/Coast, Start/Stop,
Slow Speed,
Disable
Dual Ramp, OL Select,
Fault, Fault NC, Clear Fault,
Emergency Run,
Motor Heater
Coast, Soft Stop,
Coast
Linear Speed, Pump Stop, SMB,
Ext. Brake
0...999 seconds
0
5...30
10
0.01...1.99
1.15
1.0...2200.0 A
1.0
Normal, UTS, Fault, Alarm, External
Normal
Bypass, External Brake, Auxiliary
Control, Network 1, Network 2,
Normal
Network 3, Network 4, Fan Control