MIV V4+ Mini DC Inverter R410A (220V, 8 kW)

3. Installation of Outdoor Unit

3.1 Installation place
Please keep away from the following place, or malfunction of the machine may be caused:
There is combustible gas leakage.
There is much oil (including engine oil) ingredient.
There is salty air surrounding (near the coast)
There is caustic gas (the sulfide, for example) existing in the air (near a hot spring)
A place the heat air expelled out from the outdoor unit can reach your neighbor's window.
A place that the noise interferes your neighbors every day life
A place that is too weak to bear the weight of the unit
Uneven place.
Insufficient ventilation place.
Near a private power station or high Frequency equipment.
Install indoor unit, outdoor unit, power cord and connecting wire at least 1m away from TV set or radio to
prevent noise or Install indoor unit, outdoor unit, power cord and connecting wire at least 1m away from
TV set or radio to prevent noise or
The insulation of the metal parts of the building and the air conditioner should comply with the regulation of
National Electric Standard.
CAUTION
Keep indoor unit, outdoor unit, power supply wiring and transmission wiring at least 1 meter away from
televisions and radios. This is to prevent image interference and noise in those electrical appliances. (Noise
may be generated depending on the conditions under which the electric wave is generated, even if 1 meter is
kept.)
3.2 Installation space
Air inlet
3.3 Moving and installation
Since the gravity center of the unit is not at its physical center, so please be careful when lifting it with a
sling.
Never hold the inlet of the outdoor unit to prevent it from deforming.
Do not touch the fan with hands or other objects.
Do not lean it more than 45, and do not lay it sidelong.
Make concrete foundation according to the specifications of the outdoor units.(refer to Fig.5-4)
Fasten the feet of this unit with bolts firmly to prevent it from collapsing in case of earthquake or strong
wind.(refer to Fig.5-4)
50
(Wall or obstacle)
Air inlet
>30cm
B
A
Maintain channel
>60cm
C
Air outlet