High Temperatures
Use the following cooling methods as required, taking into account the ambient temperature and the
amount of heating inside the panel.
Natural Cooling
Natural cooling relies on natural ventilation through slits in the panel, rather than using cooling devi-
ces such as fans or coolers. When using this method, observe the following points.
• Do not install the Monitor at the top of the panel, where hot air tends to stagnate.
• To provide ventilation space above and below the Monitor, leave sufficient distance from other
devices, wiring ducts, etc.
• Do not mount the Monitor in the wrong direction (e.g., vertically or upside down). Doing so may
cause abnormal heating in the Monitor.
• Do not install the Monitor directly above any heat-generating equipment, such as heaters or
transformers.
• Do not install the Monitor in a location exposed to direct sunlight.
Natural Cooling
Forced Ventilation
Forced ventilation with a fan in the top of the control cabinet.
Fan
Air filter
Forced Ventilation Method
Forced Air Circulation
Forced circulation with a fan inside the closed control cabinet.
NY-series Industrial Monitor User's Manual (W554)
OMRON
product
OMRON
product
OMRON
product
OMRON
product
5 Installation