Step Component
5
Inverter
6) Remove the terminal cover of the compressor,
assembly
and disconnect the compressor leads from the
(continued)
compressor. (Fig. 5-6)
WARNING
The quick connect terminals of the
compressor lead wires may become
loose when they are disconnected. When
reconnecting them, crimp them slightly with
radio pliers or the like and ensure they are not
loose before reinsertion. The quick connect
terminals could overheat and cause a fi re if
loose.
7) Remove the screw of the inverter assembly
and inverter fi xing plate (lower).
(M4×10, 1 ) (Fig. 5-7)
8) Lift up on the inverter assembly and move it
forward and out. (Fig. 5-8, 5-9)
Remove the inverter assembly.
Procedure
Inverter assembly
(Fig. 5-8)
Inverter assembly
(Fig. 5-9)
157
Remarks
White
White
Red
Red
Put on the
Put on the
sleeve .
sleeve.
Compressor leads
Compressor leads
(Fig. 5-6)
Notes on Compressor Leads
designated terminal.
quick connect terminals
quick connect
terminals that have been inserted once,
replace the compressor leads.
Scre (1 position)
(Fig. 5-7)
Thermostat
Thermostat
Black
Black