Step Component
4
Reactor
WARNING
replacement
Do not detach the inverter for 5 minutes after
turning off the breaker as doing so may cause
electric shocks.
1. Detachment
1) Remove the front panels, upper panel and
discharge cabinets. [Step.1 and Step.2]
2) Remove the screws of the inverter cover (B)
and reactor assembly.
(M4×10, 1 ) (Fig. 4-1)
3) Remove each wires of the reactor from reactor
terminal. (2 positions) (Fig. 4-2)
4) Disconnect the lead wires which are secured to
the clamp wire using the tie cable. (Fig. 4-2)
5) The reactor is lifted up and removed. (Fig. 4-3)
Procedure
(Fig. 4-3)
155
Remarks
(Fig. 4-1)
Clamp wire &
Reactor (CH-57-DN)
Banding band
Inverter cover (B)