Siemens SITRANS LR250 Operating Instructions Manual page 63

Radar transmitters (ma/hart)
Hide thumbs Also See for SITRANS LR250:
Table of Contents

Advertisement

Commissioning
6.2 Operating via the handheld programmer
Material
Selects the appropriate echo processing algorithms for the material [see Position Detect
(2.8.4.2.) for more detail].
Options
dK < 3.0
a)
Response Rate
Sets the reaction speed of the device to measurement changes in the target range. Use a
setting just faster than the maximum filling or emptying rate (whichever is greater).
Options
Units
Sensor measurement units.
Options
62
*
LIQUID
LIQUID LOW DK
(low dielectric liquid – CLEF algorithm enabled)
a)
Response Rate (1.3.)
*
SLOW
MED
FAST
m, cm, mm, ft, in.
Default: m
Fill rate per Minute (2.4.2.)/Empty rate per
Minute (2.4.3.)
0.1 m/min (0.32 ft/min)
1.0 m/min (3.28 ft/min)
10.0 m/min (32.8 ft/min)
SITRANS LR250 (mA/HART)
Operating Instructions, 12/2015, A5E32220602-AD