6.2

Quick Start / start-up

6.2.1
Open loop
Action
Ensure:
Before
The drive enable signal is not given (terminal 31)
power-up
Run signal is not given
Motor is connected
Power-up
Verify that Open Loop mode is displayed as the drive powers up.
the drive
Ensure: Drive displays 'Inhibit'
Enter:
Motor rated frequency in Pr 00.047 (Hz)
Enter motor
Motor rated current in Pr 00.046 (A)
nameplate
Motor rated speed in Pr 00.045 (rpm)
details
Motor rated voltage in Pr 00.044 (V) - check if
Set max
Enter:
frequency
Maximum frequency in Pr 00.002 (Hz)
Acceleration rate in Pr 00.003 (s /100 Hz)
Deceleration rate in Pr 00.004 (s /100 Hz) (If braking resistor installed,
Set accel. /
set Pr 00.015 = FAST. Also ensure Pr 10.030, Pr 10.031 and
decel. rates
Pr 10.061 are set correctly, otherwise premature 'Brake R Too Hot'
trips may be seen).
Motor
If a thermistor is connected to terminal 8, then the Analog Input 3 Mode
thermistor
(07.015) parameter must be set to Thermistor Short Cct (7), Thermistor
set-up
(8) or Therm No Trip (9).
The drive is able to perform either a stationary or a rotating autotune. The
motor must be at a standstill before an auto-tune is enabled. A rotating
autotune should be used whenever possible so the measured value of
power factor of the motor is used by the drive
WARNING
Autotune
To perform an autotune:
Set Pr 00.040 = 1 for a stationary autotune or set Pr 00.040 = 2 for a
rotating autotune
Close the Drive Enable signal (terminal 31). The drive will display
'Ready'.
Close the run signal (terminal 26 or 27). The lower display will flash
'Autotune' while the drive is performing the autotune.
Wait for the drive to display 'Ready' or 'Inhibit' and for the motor to
come to a standstill.
Remove the drive enable and run signal from the drive.
Select 'Save Parameters' in Pr mm.000 (alternatively enter a value of
Save
1000 in Pr mm.000) and press red
parameters
digital input.
Run
Drive is now ready to run
36
A rotating autotune will cause the motor to accelerate up to
base speed in the direction selected regardless of the
reference provided. Once complete the motor will coast to a
stop. The enable signal must be removed before the drive can
be made to run at the required reference.
Unidrive M700/M701 / Unidrive HS70/HS71 Control Getting Started Guide
Detail
or
connection
reset button or toggle the reset
Mot X XXXXXXXXX
No XXXXXXXXXX kg
IP55
I.cl F
°
C 40 s S1
-1
V
Hz min
kW
cosφ
A
230
50 1445 2.20 0.80 8.50
400
4.90
CN = 14.5Nm
240
50 1445 2.20 0.76 8.50
415
4.90
CN = 14.4Nm
CTP- VEN 1PHASE 1=0,46A P=110W R.F 32MN
0.02
t
100Hz
t
0.03
0.04
2
/
3
cos
R
S
σL
S
Issue Number: 2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Unidrive hs70Unidrive hs71Unidrive m701

Table of Contents