6.2
Quick Start / start-up
6.2.1
Open loop
Action
Ensure:
Before
•
The drive enable signal is not given (terminal 31)
power-up
•
Run signal is not given
•
Motor is connected
Power-up
Verify that Open Loop mode is displayed as the drive powers up.
the drive
Ensure: Drive displays 'Inhibit'
Enter:
•
Motor rated frequency in Pr 00.047 (Hz)
Enter motor
•
Motor rated current in Pr 00.046 (A)
nameplate
•
Motor rated speed in Pr 00.045 (rpm)
details
•
Motor rated voltage in Pr 00.044 (V) - check if
Set max
Enter:
frequency
•
Maximum frequency in Pr 00.002 (Hz)
•
Acceleration rate in Pr 00.003 (s /100 Hz)
•
Deceleration rate in Pr 00.004 (s /100 Hz) (If braking resistor installed,
Set accel. /
set Pr 00.015 = FAST. Also ensure Pr 10.030, Pr 10.031 and
decel. rates
Pr 10.061 are set correctly, otherwise premature 'Brake R Too Hot'
trips may be seen).
Motor
If a thermistor is connected to terminal 8, then the Analog Input 3 Mode
thermistor
(07.015) parameter must be set to Thermistor Short Cct (7), Thermistor
set-up
(8) or Therm No Trip (9).
The drive is able to perform either a stationary or a rotating autotune. The
motor must be at a standstill before an auto-tune is enabled. A rotating
autotune should be used whenever possible so the measured value of
power factor of the motor is used by the drive
WARNING
Autotune
To perform an autotune:
•
Set Pr 00.040 = 1 for a stationary autotune or set Pr 00.040 = 2 for a
rotating autotune
•
Close the Drive Enable signal (terminal 31). The drive will display
'Ready'.
•
Close the run signal (terminal 26 or 27). The lower display will flash
'Autotune' while the drive is performing the autotune.
•
Wait for the drive to display 'Ready' or 'Inhibit' and for the motor to
come to a standstill.
•
Remove the drive enable and run signal from the drive.
Select 'Save Parameters' in Pr mm.000 (alternatively enter a value of
Save
1000 in Pr mm.000) and press red
parameters
digital input.
Run
Drive is now ready to run
36
A rotating autotune will cause the motor to accelerate up to
base speed in the direction selected regardless of the
reference provided. Once complete the motor will coast to a
stop. The enable signal must be removed before the drive can
be made to run at the required reference.
Unidrive M700/M701 / Unidrive HS70/HS71 Control Getting Started Guide
Detail
or
connection
reset button or toggle the reset
Mot X XXXXXXXXX
No XXXXXXXXXX kg
IP55
I.cl F
°
C 40 s S1
-1
V
Hz min
kW
cosφ
A
230
50 1445 2.20 0.80 8.50
400
4.90
CN = 14.5Nm
240
50 1445 2.20 0.76 8.50
415
4.90
CN = 14.4Nm
CTP- VEN 1PHASE 1=0,46A P=110W R.F 32MN
0.02
t
100Hz
t
0.03
0.04
2
/
3
cos
∅
R
S
σL
S
Issue Number: 2