Quick Guide
Normal overload 150% for 1 minute
Frequency converter
Typical shaft output [kW]
Typical shaft output [hp]
Enclosure protection rating IP20
Output current
Continuous (3x380–440 V) [A]
Intermittent (3x380–440 V) [A]
Continuous (3x440–480 V) [A]
Intermittent (3x440–480 V) [A]
Maximum cable size:
2
(Mains, motor) [mm
/AWG]
Maximum input current
Continuous (3x380–440 V) [A]
Intermittent (3x380–440 V) [A]
Continuous (3x440–480 V) [A]
Intermittent (3x440–480 V) [A]
Maximum mains fuses [A]
Environment
Estimated power loss [W]
1)
Best case/typical
Weight enclosure IP20 [kg]
Efficiency [%]
2)
Best case/typical
Table 1.9 Mains Supply 3x380–480 V AC
1) Applies for dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses may
increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/
vltenergyefficiency.
2) Efficiency measured at nominal current. For energy efficiency class, see chapter 1.8.1 Surroundings. For part load losses, see www.danfoss.com/
vltenergyefficiency.
MG02BB02
Quick Guide
P5K5
5.5
7.5
M3
12.0
18.0
11.0
16.5
4/10
19.2
27.4
16.6
23.6
131.0/
166.8
3.0
98.0/
97.5
Danfoss A/S © 05/2016 All rights reserved.
P7K5
P11K
P15K
7.5
11
15
10
15
20
M3
M4
M4
15.5
23.0
31.0
23.5
34.5
46.5
14.0
21.0
27.0
21.3
31.5
40.5
16/6
24.8
33.0
42.0
36.3
47.5
60.0
21.4
29.0
36.0
30.1
41.0
52.0
See chapter 1.3.3 Fuses
175.0/
290.0/
387.0/
217.5
342.0
454.0
3.0
98.0/
97.8/
97.7/
97.5
97.4
97.4
1
P18K
P22K
18.5
22
25
30
M5
M5
37.0
43.0
55.5
64.5
34.0
40.0
51.0
60.0
34.7
41.2
49.0
57.6
31.5
37.5
44.0
53.0
395.0/
467.0/
428.0
520.0
98.1/
98.1/
98.0
97.9
21
1