1.4.2 Programming on Automatic Motor
Tuning (AMT)
Run AMT to optimise compatibility between the frequency
converter and the motor in VVC
The frequency converter builds a mathematical
model of the motor for regulating output motor
current thus enhancing motor performance.
Run this procedure on a cold motor for best
results. To run AMT, use the numeric LCP (NLCP).
There are 2 AMT modes for frequency converters.
Mode 1
1.
Enter the main menu.
2.
Go to parameter group 1-** Load and Motor.
3.
Press [OK].
4.
Set motor parameters using nameplate data for
parameter group 1-2* Motor Data.
5.
Go to 1-29 Automatic Motor Tuning (AMT).
6.
Press [OK].
7.
Select [2] Enable AMT.
MG02BB02
Quick Guide
+
mode.
Danfoss A/S © 05/2016 All rights reserved.
8.
Press [OK].
9.
The test runs automatically and indicates when it
is complete.
Mode 2
1.
Enter the main menu.
2.
Go to parameter group 1-** Load and Motor.
3.
Press [OK].
4.
Set motor parameters using nameplate data for
parameter group 1-2* Motor Data.
5.
Go to 1-29 Automatic Motor Tuning (AMT).
6.
Press [OK].
7.
Select [3] Complete AMT with Rotating motor.
8.
Press [OK].
9.
The test runs automatically and indicates when it
is complete.
NOTICE
In mode 2, the rotor rotates during the AMT progress.
Do not add any load on motor in this AMT progress.