Mitsubishi FR-A500 Series Instruction Manual page 232

Transistorized inverter: fr-a520-0.4k to 55k(-na) and fr-a540-0.4k to 55k(-na)(-ec)
Hide thumbs Also See for FR-A500 Series:
Table of Contents

Advertisement

3) Addition of Pr. 502 "error-time stop mode selection"
You can select the inverter operation if a communication line fault or a fault of the CC-Link plug-in option itself
occurs.
Parameter Number
502
(About setting)
At Fault Occurrence
Pr. 502
Fault
Setting
Operation
Indication
0
Continued
1
Continued
2
Continued
Coast to
0
stop
Decelerated
E. 3 lit after
1
to stop
Decelerated
E. 3 lit after
2
to stop
Note: 1. A communication line fault [E.OP3 (alarm data: HA3)] is a fault that occurs on the
communication line, and a fault of the CC-Link plug-in option itself [E. 3 (alarm data:
HF3)] is a communication circuit fault in the communication option.
2. The alarm output is the ABC contact output or alarm bit output.
3. When the Pr. 502 setting is 1 or 2, the deceleration time is the ordinary deceleration
setting (e.g. Pr. 8, Pr. 44, Pr. 45).
4. The acceleration time at a restart is the ordinary acceleration setting (e.g. Pr. 7, Pr. 44).
5. When the Pr. 502 setting is 2, the operation/speed command at a restart is the one given
before the fault occurrence.
6. When the setting was made to provide an alarm output, the fault definition is stored into
the alarm history.
(The fault definition is written to the alarm history when an alarm output is provided.)
When no alarm output is provided, the fault definition overwrites the alarm indication of
the alarm history temporarily, but is not stored.
After the fault is removed, the alarm indication is reset and returns to the ordinary monitor,
and the alarm history returns to the preceding alarm indication.
7. When a communication line fault occurs at the Pr. 502 setting of 2, removing the fault
during deceleration causes acceleration to restart at that point. (Acceleration is not
restarted if the fault is that of the CC-Link plug-in option itself.)
Setting Range
0, 1, 2
Error Recognition after Elapse of
Alarm
Operation
output
Not
Coast to
None
provided
stop
Not
Decelerated
None
provided
to stop
Not
Decelerated
None
provided
to stop
Coast to
E. 3 lit
Provided
stop
Provided
Decelerated
stop
after stop
to stop
Provided
Decelerated
stop
after stop
to stop
216
Minimum Setting
Increments
1
Pr. 500 Time
Alarm
Indication
Operation
output
Kept
E.OP3 lit
Provided
stopped
E.OP3 lit
Provided
Kept
after stop
after stop
stopped
E.OP3 lit
Not
Restart
after stop
provided
Kept
E. 3 lit
Provided
stopped
E. 3 lit
Provided
Kept
after stop
after stop
stopped
E. 3 lit
Provided
Kept
after stop
after stop
stopped
OPTIONS
Factory Setting
0
At Fault Removal
Alarm
Indication
output
E.OP3 kept
Kept
lit
active
E.OP3 kept
Kept
lit
active
Normal
Not
indication
active
E. 3
Kept
kept lit
active
E. 3
Kept
kept lit
active
E. 3
Kept
kept lit
active
7