Outdoor controller circuit board
PUHZ-SW75VHAR4.UK
PUHZ-SW75VHAR4-BS.UK
PUHZ-SW100YHAR4.UK
PUHZ-SW100YHAR4-BS.UK PUHZ-SW120YHAR4-BS.UK
<CAUTION> TEST POINT1 is high voltage.
CNS
(Indoor/outdoor unit
connecting wire)
63H
High pressure switch
(TEST POINT 2)
V
CC
(voltage between pins of
C821): 15 V DC
CNAC
2–4: Power supply for
outdoor controller
circuit board (230
V AC)
1–3: Power supply
for indoor and
outdoor unit con-
nection wire (230
V AC)
CN2
Connect to the outdoor
power circuit board (CN2)
1–5: Power circuit board →
Transmitting signal to the
controller circuit board
(0–5 V DC)
2–5: Zero cross signal
(0-5V DC)
3–4: Not used.
(SW75V,100/120Y)
18 V DC (SW100/120V)
6–5: 16 V DC
7–5: 16 V DC
[5: – 1,2,6,7: + ]
21S4
4-way valve
CN4
Transmission to out-
door power circuit
board (CN4)
CN52C
(Connect to the outdoor noise
filter circuit board (SW75V)/
the outdoor power circuit
board (SW100/120V))
Only for SW·VHA
OCH533D
PUHZ-SW100VHAR4.UK
PUHZ-SW100VHAR4-BS.UK
PUHZ-SW120YHAR4.UK
CNDC
280–380 V DC Connect from outdoor
power circuit board for VHA, connect
from noise filter board for YHA
CNDM
1–2: Input of low-level sound priority mode
1–3: Input of external contact point
49
PUHZ-SW120VHAR4.UK
PUHZ-SW120VHAR4-BS.UK
(CNDC)
+
SWP
SW9
Function switch
Pump down
(TEST POINT 1)
V
DC
(voltage between pins of C5E)
: 250–380 V DC
(TEST POINT 3)
V
SP
(voltage between pins of
C5A, C5B): 0 V DC (when
stopped), 1–6.5 V DC
(when operated)
(TEST POINT 4)
V
FG
(voltage between right
pins of PC5C and PC5D,
pin 3 and pin 4)
TH6
Thermistor
<2-phase pipe>
TH7
Thermistor<Ambient>
TH3
Thermistor
<Liquid>
TH4
Thermistor <Discharge>
63L
Low pressure switch
(SW100/120)
63HS
High pressure sensor
TH34
Thermistor
<Comp. surface>
LEV-A,-B
Linear expansion valve
SW4
Test operation
SW5
Function switch,
Model select
SW6
Model select
SW1
Manual defrost, detect
history record reset,
refrigerant address
SW7
Demand control setting