Webcontrol Tm Plc I/O Identifiers - CAI Networks WebControl PLC User Manual

Programmable logic controller
Table of Contents

Advertisement

TM
6.3
WebControl
The following are the valid I/O identifiers
OP1
TTL Outputs 1...8
OP2
OP3
OP4
OP5
OP6
OP7
OP8
IP1
TTL Inputs 1...8 Valid range 0 - 1
IP2
When non-blocking delay added to these input,
IP3
its value will return TRUE, if input from 0->1
IP4
longer than the delay value. For example,
IP5
IP1[1000] will return FALSE, if TTL input 1 from 0
IP6
to 1 last state change shorter than 1000ms.
IP7
IP1[1000] return TRUE only when input 1 from 0 to 1
IP8
and stay at logic 1 for longer than 1000ms.
IPINV1
TTL Invert Inputs 1...8 Valid range 0 - 1
IPINV2
This is exactly same TTL input as IP1,..IP8
IPINV3
except is inverted for filter short pulse purpose
IPINV4
its usage is like: IPINV1[1000] to filter 1->0
IPINV5
pulse shorter than 1000ms. If 1->0 pulse is shorter than
IPINV6
1000ms, it will return false. Only when input state
IPINV7
changed from 1 to 0 and stay that level for longer than
IPINV8
1000ms, the value will be TRUE.
AIP1
Analog Inputs 1...3 Valid range 0 - 1024
AIP2
AIP1 to AIP3 are built-in A/D converters.
AIP3
AIP5
Optional DS2450 provided additional analog inputs.
AIP6
Please note when DS2450 over range, its output is zero.
AIP7
When DS2450 disconnected, its value set to 1023
AIP8
T1
Temperature sensor inputs 1...8 Valid range -550 - +1250.
T2
Note that temperature values are specifies in 10's of
T3
degrees. So to test for 21.6 degrees C you would use the
T4
value 216.
T5
T6
T7
T8
TS1
Temperature sensor state 1 or 0.
TS2
1 == GOOD sensor, 0 == bad sensor
TS3
TS4
Copyright(c) 2008,-2013 CAI Networks, Inc.
WebControl
PLC I/O Identifiers
Valid range 0 - 1
TM
PLC User Guide Version 3.02.17f
27