Master Control Relay

Publication 1747-UM011G-EN-P - June 2008

Determining the Date of the SLC 500 Series A Chassis

The date of the chassis is found within the serial number imprinted on the
chassis nameplate on the right side of the chassis.
CAT
1746 - A7
SERIAL NO.
A7 -1195A1357
Right Side
Month
Year
A hard-wired master control relay (supplied by you) provides a convenient
means for emergency controller shutdown. Since the master control relay
allows the placement of several emergency-stop switches in different locations,
its installation is important from a safety standpoint. Overtravel limit switches
or mushroom head push buttons are wired in series so that when any of them
opens, the master control relay is de-energized. This removes power to input
and output device circuits.
Never alter these circuits to defeat their function, since serious
ATTENTION
injury and/or machine damage could occur.
If you are using a dc power supply, interrupt the dc side rather
IMPORTANT
than the ac side to avoid the additional delay of power supply
turn-on and turn-off. The dc power supply should receive its
power directly from the fused secondary of the transformer.
Connect the power to the dc input and output circuits through a
set of master control relay contacts.
Place the main power disconnect switch where operators and maintenance
personnel have quick and easy access to it. If you mount a disconnect switch
inside the controller enclosure, place the switch operating handle on the
outside of the enclosure, so that you can disconnect power without opening
the enclosure.