6
LP GAS CYLINDER SPECS AND INSTALLATION
The heater and its individual shutoff valve must be disconnected from
the gas supply piping system during any pressure testing of that
system at test pressures in excess of ½ PSI (3.5kPa)
The heater must be isolated from the gas supply piping system by
closing its individual manual shut-off valve during any pressure
testing of the gas supply piping system in equal or less than ½ PSI
(3.5 kPa)
The LP gas supply cylinder to be used MUST be constructed and
marked in accordance with the specifications for LP gas cylinders,
U.S. Department of Transportation (DOT) or the standard for
cylinders, spheres and tubes for the Transportation of Dangerous
Goods, CAN/CSA-B339
The propane supply cylinder system must be installed with proper
vapor withdrawal capabilities
A pressure regulator must be used in the operation with this unit.
Any replacement regulators must be of those specified by the
appliance manufacturer