Earth Resistance Display/Dial And Terminal Settings - Fluke 1662 User Manual

Electrical installation tester
Table of Contents

Advertisement

1662/1663/1664 FC
Users Manual
To measure earth resistance:
1.
Turn the rotary dial to the  position. See Table 18.
Table 18. Earth Resistance Display/Dial and Terminal Settings
Push
Button
Start the selected test
2.
Press and release
The primary display shows the earth resistance reading.
Voltage detected between the test rods shows in the secondary
display. If >10 V, the test is inhibited.
If the measurement is too noisy, Err 5 shows on the display. (The
measured value accuracy is degraded by the noise). Press
the measurement. Press
If the probe resistance is too high, Err 6 shows. Probe resistance may
be reduced if you push the test stakes further into the earth or apply
water to the earth around the test stakes.
56
Action
. Wait for the test to complete.
to return to the Err 5 display.