Auto Start enables faster testing and is a power-up option. When the Tester
detects mains voltage in the loop/line or RCD tests, the test starts automatically
without pushing
.

Loop Impedance Test with 10 mA RCD

For a Loop impedance measurement in a 10 mA RCD circuit, the tripping time
RCD test is recommended. Use a nominal test current of 10 mA and the factor
x ½ for this test.
If the fault voltage is <25 V or 50 V, dependent on the local requirement, the
loop is good. To calculate the loop impedance, divide the fault voltage by 10
mA (Loop impedance = fault voltage x 100).