Fault messages on the display
Displayed
System characteris-
fault code
tics
10
Constant mode
18
Constant mode
30
Burner blocked
38
Burner blocked
50
No DHW heating
58
No DHW heating
60
Burner blocked
68
Burner blocked
A9
Control mode without
Open Therm device
b0
Burner blocked
b8
Burner blocked
E5
Burner blocked
F0
Burner blocked
(cont.)
Cause
Short circuit, out-
side temperature
sensor
Lead break, out-
side temperature
sensor
Short circuit, boiler
water temperature
sensor
Lead break, boiler
water temperature
sensor
Terminal box cylin-
der demand fault
Terminal box cylin-
der demand fault
Short circuit, return
temperature sen-
sor
Lead break, return
temperature sen-
sor
Communication er-
ror Open Therm
device
Short circuit, flue
gas temperature
sensor
Lead break, flue
gas temperature
sensor
Internal fault
Internal fault
Troubleshooting
Measures
Check the outside tem-
perature sensor and lead
(see page 38).
Check the outside tem-
perature sensor and lead
(see page 38).
Check the boiler water
temperature sensor (see
page 39).
Check the boiler water
temperature sensor (see
page 39).
Check terminal box con-
nections and replace the
terminal box if required.
Check terminal box con-
nections and replace the
terminal box if required.
Check the return temper-
ature sensor (see
page 39).
Check the return temper-
ature sensor (see
page 39).
Check connections and
cable; replace Open
Therm device if required.
Check the sensor (see
page 41).
Check the sensor (see
page 41).
Check the ionisation elec-
trode and connecting ca-
bles.
Press "Reset" (see
page 36).
Replace control unit.
33