Commissioning, inspection, maintenance
Further details regarding the individual steps
6. Fit electrode B.
Checking and adjusting electrodes
26
4
+0,5
(cont.)
!
Please note
Tighten screws far enough
to prevent the components
being damaged and to ensure
they function correctly.
1. Check the electrode for wear and
contamination.
2. Clean the electrode with a small
brush (not with a wire brush) or sand-
paper.
3. Check the electrode gaps. If the gaps
are not as specified or the electrode
is damaged, replace and align the
electrode together with a new gas-
ket.
!
Please note
Tighten screws far enough
to prevent the components
being damaged and to ensure
they function correctly.