Delta DX-2300 Series User Manual page 51

Industrial ethernet cloud router
Table of Contents

Advertisement

Description
appointed registers in the slave, but will not
update the data to the slave
Write-only: The device update the data to the
slave when the registers values was
changed, but will not read the data from the
slave
Read/write: The device regular read data from
appointed registers in the slave, will update
the data to the slave when the registers
values is changed.
Slave ID
Set up the corresponding slave communication
port. The value is between 1 and 247.
Controller
Device types:
Delta PLC: Use this option for Delta DVP / AH
/ AS series PLCs
Other: Use this option for non-Delta DVP / AH
/ AS series PLCs.
Address Type
Depending on the selected controller type change:
Delta PLC: The address type is "D"
Other: The address type is "W"
Slave Starting Address (decimal)
Set up the slave starting address for read/write the
registers in a PLC.
Delta PLC: Enter the internal D register
number. If you need to read / write D0, please
enter 0 here.
Other: Enter the hexadecimal actual address.
For example: Holding Register: 400100, take
0100 (decimal) that is 64 (hex).
P.S. DX supports the Holding Register :
400001~465535 (Decimal)
Device Starting Address (decimal)
Set up the device starting address (decimal, input
range is from $2048 to $4095). Begin with $.
Length (1-123)
Here displays the number of the continuous
address followed by the default mapped
address.
C ha pt er 3 I ntr o duc t i on t o F u nc t i o ns
Default
N/A
Delta DVP
PLC
D
N/A
N/A
N/A
_3
3 - 2 7