Mitsubishi Electric PUZ-A12NKA7 Service Manual page 82

Split-type, heat pump air conditioners split-type, air conditioners
Hide thumbs Also See for PUZ-A12NKA7:
Table of Contents

Advertisement

SW2 setting
Discharge superheat on error
occurring
SHd
ON
32 to 360
1
2 3 4 5 6
Cooling = TH4−TH6
Heating = TH4−TH5
Sub cool on error occurring. SC
32 to 266
ON
Cooling = TH6-TH3
Heating = TH5-TH2
1
2 3 4 5 6
Thermostat-on time until error
stops
0 to 999
ON
1
2 3 4 5 6
Pipe temperature/Suction (TH32)
− 58 to 194
ON
1
2 3 4 5 6
Indoor pipe temperature/Liquid
(TH2 (3))
Indoor 3
ON
−38 to 190
1
2 3 4 5 6
Indoor pipe temperature/Cond./
Eva. (TH5 (3)) Indoor 3
−38 to 190
ON
1
2 3 4 5 6
Indoor pipe temperature/Liquid
(TH2 (4)) Indoor 4
−38 to 190
ON
1
2 3 4 5 6
OCH636A
Display detail
32 to 360 [0 to 182˚C]
(When the temperature is 100˚F or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 150˚F;
0.5 s 0.5 s 2 s
32 to 266 [0 to 130˚C]
(When the temperature is 100˚F or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 115˚F;
0.5 s 0.5 s 2 s
0 to 999
(When it is 100 minutes or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 415 minutes;
0.5 s 0.5 s 2 s
−58 to194 [−50 to 90:]
(When the coil thermistor detects 0˚F or below, "–"
and temperature are displayed by turns.)
(Example) When -10˚F;
0.5 s 0.5 s 2 s
−38 to 190 [−39 to 88°C]
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
−38 to 190 [−39 to 88°C]
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
When there is no indoor unit, "00" is displayed.
−38 to 190 [−39 to 88°C]
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
Explanation for display
1
1
15
4
15
10
82
Unit
50
Minute
˚F
[:]
˚F
[:]
˚F
[:]
˚F
[:]
˚F
[:]
˚F
[:]