"G" = TERMINAL STRIP FOR EC MOTORS NoTE: RenewAire reserves the right to make changes in the design or specifications of products at any time without notice. unless otherwise specified, dimensions are rounded to the nearest eighth of an inch.
Three 2.2-2.2 Three At AHRI 1060 standard conditions. See all AHRI certified ratings at www.ahrinet.org. specifications may be subject to change without notice. Specifications may be subject to change without notice. 1.800.627.4499 InstallatIon, operatIon and MaIntenance Manual renewaire.com renewaire.com 1.800.627.4499...
Page 4
1.800.627.4499 InstallatIon, operatIon and MaIntenance Manual For the most complete and current inFormation visit renewaire.com...
Page 5
1.800.627.4499 InstallatIon, operatIon and MaIntenance Manual renewaire.com For the most complete and current inFormation visit renewaire.com...
THE UNIT. MIN. DUCT CLEARANCE FROM DAMPER BLADE WHEN FULLY OPENED TO BE 2". SMACNA RULES PLaNNINg PLacEmENT oF THE HE1.5XIN APPLY. TOP VIEW YouR INSTaLLaTIoN The HE1.5X is designed for installation indoors. select a location that is central to the inside duct runs, and close to both the exhaust duct (to the outside) and the fresh air duct (from the outside).
HE1.5XIN INSTaLLaTIoN ducTS To THE ouTSIdE PLaNNINg YouR INSTaLLaTIoN The exhaust outlet and fresh air inlet on the waRNINg outside of the building should be at least ten feet The fresh air inlet should be at least 10’ away from apart to avoid cross-contamination.
Page 8
THE BuILdINg RadIaTEd NoISE Exhaust velocity noise is the primary cause of The HE1.5XIN is insulated with high-density unit-related noise outside the building. size the fiberglass. This provides significant attenuation exhaust duct and grille for less than 1000 Fpm of radiated sound.
Page 9
FIELd coNVERSIoN oF oPENINgS FIELd coNVERSIoN - Turn off the disconnect switch on the unit. The HE1.5XIN is designed to allow field conversion make sure electrical power is shut off to of the unit openings. This means the motorized im- the unit and disconnect switch.
Commutated motors. Consult the supplemental Installation and Operation manual(s) for these features if supplied. waRNINg standard HE1.5XIN with single phase original Le HE1.5XIN avec moteurs d’équipement d’origine equipment motors are NOT suitable for use with monophasés ne convient pas pour une utilisation avec regulateur de vitesse electronique.
HE1.5XIN INSTaLLaTIoN HE1.5XIN P1 wIRINg ScHEmaTIcS sINGLE pHAsE uNIT - sTANdARd CONTACTOR (FA) This wire omitted with UNIT DISCONNECT single-phase power POWER SUPPLY - 60 Hz FUSES (opt.) supply. SEE UNIT RATING LABEL FOR PHASE, VOLTAGE, MOTOR MCA AND MOPD.
Page 12
HE1.5XIN INSTaLLaTIoN wIRINg ScHEmaTIcS HE1.5XIN P1 IBc sINGLE pHAsE uNIT wITH INdEpENdENT BLOwER CONTROL CONTACTOR (FA) This wire omitted with UNIT DISCONNECT single-phase power FUSES (opt.) POWER SUPPLY - 60 Hz supply. SEE UNIT RATING LABEL FOR PHASE, VOLTAGE, MOTOR MCA AND MOPD.
Page 13
HE1.5XIN INSTaLLaTIoN Low VoLTagE coNTRoL SYSTEm INSTaLLaTIoN INSTRucTIoN A built-in circuit-breaker prevents damage to the This ERV is provided with a Class II 24VAC power transformer and other low-voltage components in the event of a short-circuit or overload. In extreme supply system that operates the unit’s contactor(s)
Page 14
HE1.5XIN INSTaLLaTIoN coNTRoL wIRINg NoTE: The simplified schematics below show cauTIoN ScHEmaTIcS only the relevant portions of the low-voltage Be careful if the external control system provides control circuit in the ERV unit and representational 24VAC power at its control output: make sure external control approaches.
Page 15
HE1.5XIN INSTaLLaTIoN coNTRoL wIRINg D. control System with 2 Non-powered Relay contacts: ERVs with Independent Blower Control Only: ScHEmaTIcS use this schematic if the external control system provides no voltage or current at its output contacts. Connect the two blue leads together. Connect the red lead to one side of each of the output contacts.
HE1.5XIN STaRT-uP mEaSuRINg aIR FLow EquIPmENT REquIREd NoTE: Be sure to remove cap from pressure port A magnehelic gauge or other device capable of before inserting tubing. Insure tubing is well seated • measuring 0 to 1.5 in. water of differential pressure.
Page 17
HE1.5XIN V15.xlsx 14+16x20x2 MERV 8 (IOM) STaRT-uP FILTER SPEcIFIcaTIoNS mEaSuRINg aIR FLow • (2) 14” x 20” x 2” and (2) 16” x 20” x 2” (nominal) pleated filters. Actual size: 13.5” x 19.5” x 1.75” and 15.5” x 19.5” x 1.75”.
HE1.5XIN maINTENaNcE SERVIcE PaRTS HE1.5XIN(H & V) Horizontal and Vertical Units HE1.5XINH sHOwN www.renewaire.com (800) 627- 4499 support@renewaire.com RENEwaIRE.com 1.800.627.4499 InstallatIon, operatIon and MaIntenance Manual...
Page 19
HE1.5XIN maINTENaNcE REquIREmENTS waRNINg danger of Electrical shock when servicing an installed unit. aLwaYS dIScoNNEcT PowER SouRcE BEFoRE SERVIcINg! more than one disconnect switch may be required. proper wiring size selection and wiring Installation are the Responsibility of the Electrical Contractor.
Page 20
Every time. anywhere. At RenewAire — unlike other ventilation suppliers — advanced ventilation solutions are all we do. Our sole passion. which is why for all commercial projects, we are the “V” in HVAC...