Page 1
CA SERIES ERV Installation, Operation and Maintenance Manual CA2XIN CA3XIN CA4XIN CA4XIN shown...
Page 2
CA-Series Indoor WARNING WARNING Danger of carbon monoxide poisoning! Outside air intake RISK OF FIRE, ELECTRIC SHOCK, OR INJURY. should be 10' (minimum) away from sources of carbon mon- oxide or other toxic gases such as chimneys, furnace, or water OBSERVE ALL CODES AND THE FOLLOWING: heater exhausts.
Page 3
The completed Locate the RenewAire unit label found on the outside of the unit. document is to be turned NOTE: This information is for purposes of identifying the unit-specific option data from the over to the owner after Option Code.
Page 4
96" L x 47" W x 40" H & Weight (on pallet) 350 lbs. 500 lbs. 620 lbs. Some ventilation projects require more flexibility than packaged ERVs allow. RenewAire offers both Filters: MERV 8: Thermal Performance Ratings G5 2015.2.xlsx 3 Cores (IOM) Total qty. 4 Total qty. 6 Total qty.
Page 5
RENEWAIRE.COM FOR THE MOST COMPLETE AND CURRENT INFORMATION VISIT 1.800.627.4499...
The CA-Series Indoor cabinet(s) do not contain blowers. Therefore, two blowers must be EA = Exhaust Air to out- installed as part of the system. Several ducts must also be installed. side. FIGURE 1.2.0 OPPOSITE SIDE AIRFLOW ENTRIES www.renewaire.com (800) 627- 4499 support@renewaire.com www.renewaire.com (800) 627- 4499 support@renewaire.com...
The filters must cover the INLET FACES of the cores. Filter racks are provided at each face to handle all possible airflow configurations. FIGURE 1.3.0 CA-SERIES INDOOR CABINET APPLICATION EXAMPLE www.renewaire.com (800) 627- 4499 support@renewaire.com 1.800.627.4499...
With Push-Push or Pull-Pull blower orientations, there is generally no need to review the static pressure differences between the two airstreams. FIGURE 2.1.0 “PUSH-PUSH” BLOWER ORIENTATION FIGURE 2.1.1 “PULL-PULL” BLOWER ORIENTATION www.renewaire.com (800) 627- 4499 support@renewaire.com www.renewaire.com (800) 627- 4499 support@renewaire.com...
INSTALLATION CA-Series Indoor 2.2 BLOWER SIZING Most “low airflow” problems in the field are caused by under-sized blowers. Systems can under-perform if the designer does not make sufficient allowance for duct leakage, variations in duct layout from ideal design, less-than-ideal blower outlet conditions, dirty filters, and the like. In general, ventilation systems with energy-recovery components tend to need blowers with relatively high static pressure curves.
USE 1-1/2" SELF TAPPING SCREWS AT BOTH ENDS OF CABINET FIGURE 2.4.0 STACK AND SECURE CABINETS www.renewaire.com (800) 627- 4499 support@renewaire.com 2. Fabricate and attach four sets of flanges on the sides of the stacked cabinets. Each flange will enclose one opening of each cabinet. See Figure 2.4.1.
INSTALLATION CA-Series Indoor 3. Connect ductwork to the flanges. See Figure 2.4.3. FIGURE 2.4.3 CONNECT DUCTWORK www.renewaire.com (800) 627- 4499 support@renewaire.com 2.5 SPECIAL CONSIDERATIONS FOR OUTSIDE AIR AND EXHAUST AIR DUCTS WARNING Danger of carbon monoxide poisoning! Outside air intake should be 10' (minimum) away from sources of carbon monoxide or other toxic gases such as chimneys, furnace, or water heater exhausts.
OPERATION CA-Series Indoor 3.0 OPERATION NOTE: Some juris- dictions may allow 3.1 PRINCIPAL OF OPERATION less separation, or The CA-Series Indoor has one basic purpose: to exhaust air from a structure and bring in fresh may require more. air from outside, while transferring heating or cooling energy from the exhaust air to the fresh Check with your local code air.
MAINTENANCE CA-Series Indoor 3.7 FIELD MEASUREMENT OF AIRFLOW THROUGH CORES NOTE: The filters supplied in the unit In most cases, conventional test-and-balance methods will be used to confirm proper airflows are usually able to in the entire ventilation system. keep the energy exchage Sometimes it is desirable to estimate airflow in the CA-Series Indoor cabinets themselves, for core clear for several example, to localize the location of duct leaks.
MAINTENANCE CA-Series Indoor IMPORTANT Make sure all four lips of the core enter the receiver channels when re-inserting the core into the unit. CAUTION Filters must be used or the energy exchanger core will become blocked by dust and the unit will not do its job.
To contact RenewAire Customer Service: Call 800-627-4499 RenewAireSupport@RenewAire.com Email: Remember that RenewAire Customer Service can only assist with the products sold by RenewAire, it cannot resolve engineering issues that result from air handling system design by others. 1.800.627.4499...
Page 20
About RenewAire For over 30 years, RenewAire has been a pioneer in enhancing indoor air quality (IAQ) in commercial and residential buildings of every size.This is achieved while maximizing sustainability through our fifth-generation, static-plate, enthalpic-core Energy Recovery Ventilators (ERVs) that optimize energy efficiency, lower capital costs via load reduction and decrease operational expenses by minimizing equipment needs, resulting in significant energy savings.