YASKAWA Varispeed F7 Instruction Manual page 46

Hide thumbs Also See for Varispeed F7:
Table of Contents

Advertisement

Table 2.3 Closed-loop Connector Sizes (JIS C2805) (200 V Class and 400 V Class)
2
Wire Thickness (mm
)
0.5
0.75
1.25
2
3.5/5.5
8
14
22
30/38
50/60
80
100
100
150
200
325
1. Determine the wire size for the main circuit so that line voltage drop is within 2% of the rated voltage. Line
voltage drop is calculated as follows:
Line voltage drop (V) =
IMPORTANT
2. Use a closed-loop connector (made by J.S.T. Mfg. Co., Ltd. or an equivalent) for the main circuit input and
output terminals of Inverters of 200V 11 kW or more and those of 400V 22 kW or more.
Terminal Screws
M3.5
M4
M3.5
M4
M3.5
M4
M3.5
M4
M5
M6
M8
M4
M5
M6
M8
M5
M6
M8
M6
M8
M6
M8
M8
M8
M10
M10
M12
M12 x 2
M16
3
x wire resistance (W/km) x wire length (m) x current (A) x 10
Wiring Main Circuit Terminals
Size
1.25 to 3.5
1.25 to 4
1.25 to 3.5
1.25 to 4
1.25 to 3.5
1.25 to 4
2 to 3.5
2 to 4
2 to 5
2 to 6
2 to 8
5.5 to 4
5.5 to 5
5.5 to 6
5.5 to 8
8 to 5
8 to 6
8 to 8
14 to 6
14 to 8
22 to 6
22 to 8
38 to 8
60 to 8
60 to 10
80 to 10
100 to 10
100 to 12
150 to 12
200 to 12
325 to 12
325 to 16
-3
11
2-

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents