3.3

Modifying SM 335 parameters in RUN

HW Config

You can modify certain (dynamic) parameters while the CPU is in RUN state.
You can transfer the SM 335 parameters by calling
● SFC55 "WR_PARM" (central, distributed PROFIBUS)
● SFB53 "WRREC" (central, distributed PROFIBUS/PROFINET)
For additional parameterization options, refer to the System and Standard Functions for S7-
300/400 (http://support.automation.siemens.com/WW/view/en/1214574) Reference Manual.
Parameters
The SM 335 parameters have a length of 16 bytes which are split into two data sets (DS0
and DS1).
Save the SM 335 parameters (complete DS1 that is to be transferred to the module) to a
data area on the CPU (e.g. bit memory, data block). Transfer the parameters to SM 335 with
the help of SFC 55 "WR_PARM" or SFB53 "WRREC".

Data sets

The SM 335 parameters are stored in two data sets (DS0 and DS1).
Data set 0 (DS0)
Data set 0 of SM 335 has a length of 2 bytes and contains the static parameters of SM 335.
You cannot modify those parameters.

Data set 1 (DS31)

Data set 1 contains the dynamic parameters of SM 335 which you can modify.
NOTICE
The transfer always has to include the entire data set 1 (bytes 0 to 13).
SM 335 - High-speed analog mixed module for SIMATIC S7-300
Manual, 02/2009, A5E02409063-01
Data exchange with SM 335
3.3 Modifying SM 335 parameters in RUN
47