Analog Value To Be Output; Comparator Time (Ds1, Byte 1) - Siemens SIMATIC S7-300 Manual

High-speed analog mixed module
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Data exchange with SM 335
3.3 Modifying SM 335 parameters in RUN
Data set 1
The parameters which you can toggle dynamically are stored in data set 1 of SM 335.
Table 3- 12
Byte
0
1
2
3
4
5
6
7
8
9
10
11
12
13

Analog value to be output

SM 335 outputs the default values at up to 3 analog outputs for comparator 1 or 2; refer to
chapter Special operating mode "Comparator" (Page 79).

Comparator time (DS1, byte 1)

SM 335 cannot generate a hardware interrupt for the end of the cycle while comparator 2
mode is enabled. It can therefore happen that SM 335 does not generate an end of cycle
interrupt for a longer time.
You can define the maximum comparator activation time by setting the comparator time.
After the active comparator time has expired, SM 335 automatically returns to the
"conditional cycle" or "free cycle" mode.
Define the comparator time in milliseconds (1 = 1 ms, 2 = 2 ms, up to 0 = 256 ms).
54
Data set 1 of SM 335 for the special mode "Comparator"
Content
Analog value 1 high byte to be output
Analog value 1 low byte to be output
Analog value 2 high byte to be output
Analog value 2 low byte to be output
Analog value 3 high byte to be output
Analog value 3 low byte to be output
Comparison value "Comparator 1" high byte
Comparison value "Comparator 1" low byte
Comparison value "Comparator 2" high byte
Comparison value "Comparator 2" low byte
Comparator time
Dynamic measuring cycle control
Comparator - check byte
Reserved
SM 335 - High-speed analog mixed module for SIMATIC S7-300
Manual, 02/2009, A5E02409063-01