Chapter 8
Configure PhaseManager
Minimum System
Requirements
Equipment Phase
Instructions
118
To develop PhaseManager programs, you need:
• a CompactLogix controller with firmware revision 16.0 or later.
• a communication path to the controller.
• RSLogix 5000 programming software, version 15.0 or later.
To enable PhaseManager support, you need the full or professional editions of
RSLogix 5000 programming software or the optional PhaseManager add-on
(9324-RLDPMENE) to your RSLogix 5000 programming software package.
With CompactLogix controllers, you can issue many ladder diagram (LD) and
structured text (ST) instructions to begin various equipment phases.
Instruction Code
PSC
PCMD
PFL
PCLF
PXRQ
PRNP
PPD
PATT
PDET
POVR
Rockwell Automation Publication 1769-UM011H-EN-P - April 2012
Instruction
Signal a phase that the state routine is complete so go to the next state
Change the state or substate of a phase
Signal a failure for a phase
Clear the failure code of a phase
Initiate communication with RSBizWare Batch software
Clear the NewInputParameters bit of a phase
Set up breakpoints within the logic of a phase
Take ownership of a phase to either:
• prevent another program or RSBizWare Batch software from commanding a
phase
or
• make sure another program or RSBizWare Batch software does not already own
a phase
Relinquish ownership of a phase
Override a command