Installation Procedure - Pro-face GP4000 SERIES Installation Manual

This installation guide describes gp4000 series except gp-4100 series, gp- 4201tm and gp-4301tm
Hide thumbs Also See for GP4000 SERIES:
Table of Contents

Advertisement

Installation
When installing the GP unit in a slanted position with an incline more than 30°, the
ambient temperature must not exceed 40 °C (104 °F). You may need to use forced
air cooling (fan, A/C) to ensure the ambient operating temperature is 40°C or less
(104 °F or less).
For easier maintenance, operation and improved ventilation, install the GP unit at
least 100 mm (3.94 in.) away from adjacent structures and other equipment as
shown in the following illustration.
The holes on the rear of the GP unit (except GP-4200 Series) are not
correspondent with VESA 75mm standards. Do not attach the GP unit to the
commercial-type VESA arm.

2. Installation Procedure

PANEL UNSTEADY WHEN UNSECURED
• Keep GP unit stabilized in the panel-cut while you are installing or removing
the screw fasteners.
Failure to follow the instruction can result in equipment damage.
Step
Action
1
Place the GP unit on a clean and level surface with the display facing
downward.
2
Check that the GP unit's gasket is seated securely into the gasket's
groove, which runs around the perimeter of the panel frame.
Note: It is strongly recommended that you use the installation gasket, since it
absorbs vibration in addition to repelling water.
For the procedure for replacing the installation gasket, refer to "GP4000
Series Hardware Manual".
20
mm
in.
100
100
3.94
3.94
NOTICE
100
3.94