Safety, approvals, EMC

7.4 EMC

7.4
EMC
Electrostatic discharge
Electromagnetic fields
High-speed transient dis-
turbance variables (burst)
Surge voltages
High-frequency fields
Magnetic fields
Voltage dips
Voltage interruptions
Emitted interference
Line harmonics limit
Generic standards
52
6EP3333-8SB00-0AY0
(24 V/5 A)
6EP3334-8SB00-0AY0
(24 V/10 A)
EN 61000-4-2
8 kV contact, 8 kV air
EN 61000-4-3
80 ... 1000 MHz 25 V/m
1000 ... 2700 MHz 10 V/m
EN 61000-4-4
4 kV at line supply connections
2 kV at the DC output
EN 61000-4-5
3 kV symmetrical at the line
supply connections
6 kV symmetrical at the line
supply connections
500 V symmetrical/asymmetrical
on DC output cables
EN 61000-4-6
10 V; 0.15 ... 80 MHz
EN 61000-4-8
30 A/m; 50 Hz
EN 61000-4-11
-
EN 61000-4-11
-
EN 55022
Class B
EN 61000-3-2
Class A
EN61000-6-2
Noise immunity for industrial environments
EN61000-6-3
Emission for residential areas
6EP1336-3BA10 (24 V/20 A)
8 kV contact, 8 kV air
80 ... 1000 MHz 25 V/m
1000 ... 2700 MHz 10 V/m
4 kV at line supply connections
2 kV at the DC output
3 kV symmetrical at the line supply
connections
5 kV asymmetrical at the line supply
connections
500 V symmetrical/asymmetrical on
DC output cables
10 V; 0.15 ... 80 MHz
30 A/m; 50 Hz
100 % for 20 ms
60 % for 200 ms
30 % for 500 ms
100 % for 5000 ms
SITOP PSU8200 1ph