ACCESSORY KIT INSTALLATION INSTRUCTIONS
HA 300, HB 360 / 480 / 600, HF-25, HL-30 / -40 / -50 Models
GENERAL
These split-system condensing units are designed to
operate at ambient temperatures down to 40°F. This
accessory will insure safe operation at ambient temper-
atures down to 0°F. The VLT6000 control monitors the
refrigerant system and will vary the condenser fan
speed based on the discharge pressure. One controller
is required for each fan to be controlled. Therefore, two
accessory kits are required for each unit. This instruc-
tion provides all the necessary information to properly
field-install a low ambient accessory on the condensing
units listed in Table 1. Components that are supplied in
the respective accessory are listed in Table 2, and pic-
tured in Figure 1.
TABLE 1: APPLICATION DATA
ACCESSORY MODEL #
2LA04702658
2LA04702858
2LA04702958
2LA04703058
TABLE 2: ACCESSORY COMPONENTS
ITEM
QTY.
PART NO.
*
1*
473-24615-00X*
1
ea
2
1 ea
025-38680-000
3
1 ea
025-38681-000
4
1 ea
025-37466-000
5
1 ea
023-20566-000
6
2 ea
021-15529-000
7
1 ea
025-10209-000
8
2 ea
025-14284-000
9
6 ea
025-09607-000
10
1 ea
025-37455-000
2 ea
025-37425-575
11
2 ea
025-37474-575
*.
"X" denotes Model number needed for application.
†. Crankcase Heaters supplied are dependent on accessory
ordered.
Unitary Products Group
Low Ambient Accessory
For Air Cooled Split-System Air Conditioners
VOLTAGE
UNIT
575
HA 300, HF -25
575
HB 360, HL -30
575
HB 480, HL -40
575
HB 600, HL -50
DESCRIPTION
VLT6000 Condenser Fan Speed
Control and Enclosure
Pressure Transducer
Wire Harness Assembly
Power wire Harness
Tee Connector
Screw HEX ¼-14 X.75
7/8 Bushing
1 3/8 Bushing
Wire Tie
0º Degree Switch
30/40 Ton Crankcase Heater
25/50 Ton Crankcase Heater
FIGURE 1 - ACCESSORY COMPONENTS
The 2LA047 series low ambient accessories are
intended for use with the 25-50 Ton Split System con-
densing units only. UPG cannot guarantee proper
operation for any application of this VLT6000 control-
ler for other equipment or applications. Contact your
local branch or distributor for any application related
questions.
Improper installation, adjustment, service or mainte-
nance can cause injury or property damage. There-
fore, only a qualified installer or qualified service
personnel should perform this conversion.
If the unit is connected to power sources, make sure
that all electrical power to the unit has been discon-
nected.
035-20209-000-A-0904

Advertisement

loading
Need help?

Need help?

Do you have a question about the HA 300 and is the answer not in the manual?

Questions and answers

Summary of Contents for Unitary products group HA 300

  • Page 1 ACCESSORY KIT INSTALLATION INSTRUCTIONS Low Ambient Accessory For Air Cooled Split-System Air Conditioners HA 300, HB 360 / 480 / 600, HF-25, HL-30 / -40 / -50 Models GENERAL These split-system condensing units are designed to operate at ambient temperatures down to 40°F. This accessory will insure safe operation at ambient temper- atures down to 0°F.
  • Page 2 (provided). Figure 6. • Hand thread the tee to the discharge line port. • Tighten and secure the connection, making sure 9. Remove the terminal access cover. See Figure 5. the transducer is mounted vertically. See Figure Unitary Products Group...
  • Page 3 Connect Red Wire from Transducer to Terminal • Disconnect wire 136/BLK from terminal (T1) on (50). contactor (M5). • Connect Bare (shield) Wire from Transducer to • Disconnect wire 137/BRN from terminal (T2) on Grounding Terminal. contactor (M5). Unitary Products Group...
  • Page 4 17. Replace terminal access cover on VLT6000 con- NOTE: VLT6000 trol. See Table 3 for the parameter settings in the 18. Replace lid on VLT6000 enclosure. drive. For specific instructions on the VLT6000, refer to the Danfoss manual shipped with the kit. Unitary Products Group...
  • Page 5 284 / BL 286 / BL FIGURE 8 - LAS-LOW AMBIENT SWITCH WIRING LOCATIONS * Single control board (RB1) applies to 25-Ton unit only. **Dual control board (RB1 & 2) apply to 30, 40 & 50 Ton units. Unitary Products Group...
  • Page 6: Control Terminals

    154 / BK 91, (L1) (U), 96 M7 - 2 155 / BR (V), 97 92, (L2) M7 - 3 (W), 98 156 / PR 93, (L3) CONTROL TERMINALS Pressure Transducer System 2 FIGURE 9 - SIMPLIFIED WIRING DIAGRAM Unitary Products Group...
  • Page 7 Transmitter voltage at maximum pressure Feedback Pressure transmitter 2 is wired to terminal 54 0 VDC Transmitter voltage at minimum pressure 10 VDC Transmitter voltage at maximum pressure No operation Assumes terminal 60 is not used 0 mA Unitary Products Group...
  • Page 8 Proportional gain Integral time Differential time (leave OFF) 0.02 First order filter on feedback signal Subject to change without notice. Printed in U.S.A. Copyright © by Unitary Products Group 2004. All rights reserved. Supersedes: Nothing 035-20209-000-A-0904 Unitary 5005 Norman Products...