INSTALLATION SINGLE PACKAGE INSTRUCTION WATER COOLED AIR CONDITIONERS EMBASSSY SERIES TABLE OF CONTENTS MODELS C*ED060A, 090A, 120A, & 180A GENERAL ....... . . 3 CAUTIONS, NOTES AND WARNINGS .
Drain connections are made on the right side only for all units except the ED180, which can be made form either side. Excessively low GPM and high water temperature may result in H.P. Cutout trip, 325 PSI. Units are not intended for outdoor installation. CAUTIONS, NOTES AND WARNINGS Unitary Products Group...
STRICT COMPLIANCE WITH THE ENCLOSED • Form 550.12-N10.7U Hot Water Coil and Non-Freeze INSTALLATION INSTRUCTIONS AND ANY Steam Coil APPLICABLE LOCAL, STATE, AND NATIONAL • Form 560.20-N1.5 Water Regulating Valve CODES INCLUDING BUT NOT LIMITED TO, BUILDING, ELECTRICAL AND MECHANICAL CODES. Unitary Products Group...
This is necessary for access to the electrical box, con- Supply and return air ducts should be used, con- denser water piping and the removal of compressor ship- nected to the unit with asbestos cloth collars, and ping blocks. lined with sound absorbing material. Unitary Products Group...
5 Ton Refrigerant-22, lbs. - oz. System - 1 5-14 PERATING HARGE 12-0 System - 2 5-14 The 10-Ton system is wired for first stage operation. The refer to Table 15 for additional blower motor and drive data. Unitary Products Group...
Convert kW to MBH per the following equation and deduct this equivalent heat from the gross cooling ratings. BLOWER MOTOR kW x (3.415 MBH / kW) = Blower Motor Heat (MBH) Compressor kW only. For total unit kW, add the kW requirement of the supply air blower per Table 8. Nominal Rating Unitary Products Group...
Convert kW to MBH per the following equation and deduct this equivalent heat from the gross cooling ratings. BLOWER MOTOR kW x (3.415 MBH / kW) = Blower Motor Heat (MBH) Compressor kW only. For total unit kW, add the kW requirement of the supply air blower per Table 8. Nominal Rating Unitary Products Group...
Compressor kW 0.97 0.99 1.00 1.01 1.02 1.10 1.04 1.00 0.97 0.95 TABLE 7: CONDENSER WATER PRESSURE DROP CONDENSER PRESSURE CONDENSER PRESSURE MODEL MODEL WATER GPM DROP PSI WATER GPM DROP PSI CED060 CED120 CED090 22.5 CED180 Unitary Products Group...
The CED060A46 has a 1 HP blower motor that can operate 1.15 BHP providing the unit is not equipped with a hot water or steam coil. Exceeds the BHP limitation of the standard, factory RPM range for the standard, fac- mounted blower motor. tory-mounted drive components Unitary Products Group...
A d d 2 7 " T o U n i t H e i g h t W h e n U s e d 2 - 3 / 1 6 FIGURE 4 : UNIT DIMENSIONS - CED180 See Table 11 for Minimum Clearances on page 14. Unitary Products Group...
Overall dimension of the unit will vary if an electric heater or a supply air plenum is used Allow enough clearance to trap the auxiliary drain line This dimension is required for removal of the coil. Only 26” is required for normal servicing. Unitary Products Group...
(turns open) for the supply air motor pulley can be determined form Table 12. Before replacing panels, see paragraphs on Duct Con- nection and Drain connections. Each motor pulley has: Replace panels. A threaded barrel with two flats (or notched recesses 180 degrees apart. Unitary Products Group...
If the CFM is above or below the specified value, the supply air motor pulley may have to be re-adjusted. After on hour of All pulleys are factory aligned. Unitary Products Group...
Filter must be removed on CED060 unit only before read- ings are taken. CED060 9-1/2 2-1/4 10-1/4 CED090 CED120 CED180 1-3/4 13-3/4 NOTE:Shut down the refrigerant system before taking any test measurements to assure a dry evaporator coil. Unitary Products Group...
(not in series), the stop valves may be used to equalized COLLASPE OF THE TUBES INSIDE THE the pressure drop through every parallel circuit for even REFRIGERANT TO WATER HEAT EXCHANGER condenser water distribution. DUE TO LACK OF WATER FLOW. Unitary Products Group...
Connect wires to terminal block 4TB located on left side of Completely assembled, evacuated, charged and leak control box (See Figure 14). tested. NOTE:Refer to wiring diagram inside control box cover for proper connections. Unitary Products Group...
CED installation. Water regulating valves are shipped separately for field installation. Accessory kits 1WR0413, 1WR0402, and 1WR0403 are used on the CED060, CED090 and CED120, and CED180 respectively. Unitary Products Group...
If freezing is a problem, provisions for draining the sys- tem should be made. In addition, it may be desirable to Avoid using long runs of pipe exposed to the sun. run as much of the piping indoors as possible. Unitary Products Group...
Move fan switch to “ON”. Evaporator blower motor 11. If electric heat is installed on unit – set system switch to should start. “HEAT” and raise room thermostat until 1 stage of heat Unitary Products Group...